Cart
AD-310 configure
TK-313 configure
TK-312 configure
ER-214 configure
ZMF-100-IR configure
TK-308 configure
TK-303 configure
TK-307-0 configure
EE-24 configure
LU-1X0 configure
ÜTA-32 configure
XR-4x2 configure
EF2...5 configure
TK-30X configure
ZMF-20x Serie configure
ViscoScope® VA-100 configure
TK-300 configure
QFS-2X configure
TK-301 PTFE configure
KG-2XX configure
ViscoScope® VA-300 configure
ZS-1 configure
T-200.L 230V configure
TK-101 EX configure
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel : IP 65
- Operating temperature : – 20...+ 60 °C
- nominal voltage : Weitbereichsnetzteil; 20 V DC ... 230 V AC
- Power consumption : max. ca. 3 VA
- Output contact : 2 Schließer / NO
- Switching voltage : max. 250 V AC, 300 V DC
- Switching current : max. 3 A , DC min. 30 mA
- Switching capacity : max. 50W, 100 VA
- Unregulated auxiliary voltage source : 15...20 V DC / 20 mA
- Display : LED 14 mm, 5-stellig
- Dimensions : 96x48x100 mm
- Weight : ca. 200 g
- Panel cut-out : H:45+0,6mm, B:92+0,8 mm
Equipment
- Measuring input current : 0(4)...20 mA DC
- Measuring input voltage : 0(2)...10 V DC
- Measuring input Potentiometric voltage divider : 1...100 kΩ
- Display : LED 14 mm, 5-stellig
- operation : Folientasten
- Display range : -19999...32000
- data backup : EEPROM
- measurement uncertainty : ±1 % oder ±1 Digit
- analogue output : 0 (4)...20 mA
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA, 2W
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0-4...10 kW
Output
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Current output : 0/4... 20 mA bezogen auf die Masse des Eingangs
- Voltage output : 0/2... 10 V
- Mounting : Tragschiene nach EN 50022
- Weight : 175 g
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm
Product features
- Measuring principle : optisch, NDIR (nicht-dispersive Infrarot-Absorptionsmessung)
- Operating voltage : 24 V DC / 100 mA
- Heating time : ca. 5 min
- Response time : ca. 30 s
- Repeatability : +/- 1%
- Housing : Aluminium (rot) IP54
- Weight : ca. 500g
- Shaft range : 4,27 - 4,35 µm (4270-4350 nm)
- Gas ingress : per Diffusion
ambient conditions
- Operating temperature range : -10...+50 °C
- Storage temperature range : -40...+100 °C
- RelativeHumidity : 15..95 %
- Air pressure : 900...1100 hPa
TK-308
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 11,12, 15, 17
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
Operating temperature
- PVC : max. 60 °C
- PE : max. 80 °C
- PP : max. 90 °C
MaterialDensity
- Type 11 : 0,60 g/cm³
- Type 12 : 1,00 g/cm³
- Type 15 : 0,59 g/cm³
- Type 17 : 0,63 g/cm³
TK-303
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class : IP 65
- Float type : 03, 04, 09
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar (Kugel) max. 15 bar (Zylinder)
- Resolution : 7,5 mm | 10 mm
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
- Type 09 : 0,76 g/cm³
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
- Connection aluminium box : H30 x B50 x T45 mm
- Connection polyester box : H56 x B80 x T75 mm
- connection cable : 1000 mm PUR blau
- Protection class Socket : IP65
- Material Sliding tube : VA 1.4571
- Material of the angle fastening : VA 1.4408
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
- connection thread : G 1/2” Standard | G 3/4” | G1”
- Cable : TPK (Standard) | SIL (Silikon) | FEP (Teflon)
- rod length : max. 6.000 mm
- Operating pressure : max. 40 bar
Material
- electrode body : Edelstahl 1.4571
- Process connection : Edelstahl 1.4571
- Coating : PTFE
- electrode rod : Edelstahl 1.4571
- on request : Hastelloy C | Tantal
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
- connection : G 1” (andere Gewinde auf Anfrage)
- max.length guide tube : siehe Diagramm
- Operating temperature : atmosphär. Bedingungen
- Operating pressure : atmosphär. Bedingungen
- media density : siehe Eintauchtiefe
- Number of contacts : beliebig
- Contact load : max. 10 VA, max. 230 V AC
- Length : max. 1750 mm
Material
- Sight tube : PVC transparent
- connection : PVC-Verschraubung mit PTFE-Stangenführung
- Guide rod : Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
- float : PE / PP
XR-4x2
Electrode relay with ATEX and WHG approval
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- Weight : ca. 150g
- ltdata. :
Power supply
- nominal voltage : siehe Typenschlüssel
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
- Switching delay : siehe Typenschlüssel
- Sensitivity range : siehe Typenschlüssel
Output
- Contacts : potentialfreie Wechselkontakte
- Switching voltage(min) : 5 V
- Switching voltage (max) : 250 V AC / 150 V DC
- Overvoltage category : EN 61010-1 Kategorie III
Switching current
- Switching current : min. 5 mA
- Switching current : max. cos φ =1 5 A
- Switching current : max. cos φ = 0,7 3 A/AC
- Switching current : max. cos φ = 1
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
TK-30X
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties
- connection : Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
- connection thread : G 3/8”, G 1/2”, G 1”, G 1 1/2”, G 2”, G 3”
- connection cable : LiYY max. 80 °C | Silikon max. 130 °C
- Sliding tube length : max. 6000 mm
- Operating temperature : max. +60...+130 °C | min. –20...–10 °C je nach Ausführung
- Operating pressure : max. 20 bar je nach Ausführung
- media density : siehe Schwimmerdaten
- Viscosity : < 100 cp
- Switching hysteresis : ca. halbe Auflösung
- Resolution : 7,5 mm, 10 mm, 15 mm, 20 mm oder 1 %, 2 %, 5 % je nach Ausführung
- Total resistance : ca. 5 kΩ
- Measuring voltage : max. 24 V
- Measuring current : max. 5 mA
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
ZMF-20x Serie
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-20X series includes sensors & transmitters for measuring gas concentrations of various gases such as CO2, methane, propane and SF-6.
This makes the sensors suitable for many applications. The ZMF-20X gas sensors are designed to be extremely rugged & suitable for use in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2-Zertifizierung, ATEX-Zertifizierung (auf Anfrage)
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m (weitere Längen auf Anfrage)
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
ViscoScope® VA-100
Inline Viscometer
Maintenance-free inline viscosity sensor for precise and reliable real-time measurement of viscosity directly in the process.
Properties
- Material : 1.4571 / 1.4404 (316Ti / 316L)
- Protection class : IP65
- Process temperature : -10°C … +130°C | (integriertes Pt100 im Messfühler)
- max. process pressure : Vakuum ... 64 bar
- Process connections : NPT | M48 | Varivent® | Tri-Clamp
- Cable length sensor - transmitter : Max. 1.000 Meter
- max. flow velocity : 5 m / sec
- Ex approval : II 1/2G Ex ia IIC T6...T3 Ga/Gb | (optional)
Sensor types
- Sphere : VA-100B
- Cylinder : VA-100C
Repeatability
- VA-100B : ± 0,5% | ± 1 Digit
- VA-100C : ± 0,3% | ±1 Digit
Measuring ranges
- VA-100C : 0,1 - 2.500 mPa·s x g/cm³
- VA-100B : 10 - 25.000 mPa·s x g/cm³
Probe dimensions
- VA-100C : Ø 32 x 145 mm
- VA-100B : Ø 32 x 120 mm
installation positions
- Reservoir :
- tanks :
- Pipe :
- flow cell :
- Installation is position-independent :
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
- details : folgen
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
- connection : Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 10 (14)
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
- CE marking : siehe Konformitätserklärung
Operating temperature
- PV : max. 60°C
- PE : max 80 °C
- PP : max. 90°C
MaterialDensity
- Type 10 : 0,72 g/cm³
- Type 14 : 0,72 g/cm³
- Type 18 : 0,82 g/cm³
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
- Protection class EN60529 : IP68
- Material Float : VA 1.4571
- Material hose : Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
- Operating temperature : max. + 150 °C
- media density : ρ ≥ 0,8g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
- Operating pressure (QFS-20) : max. 15 bar
- Operating pressure (QFS-21) : max. 6 bar
TK-301 PTFE
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 16
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 120 °C
- Operating pressure : max. 3 bar
- media density : 0,79 g/cm³
- Resolution (depending on type) : 7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
Aero_aH100
Exhaust air fan with integrated dehumidification control for automatic room dehumidification
Dehumidification control, including integrated indoor and outdoor climate sensor. Controlled dehumidification takes place by comparing the indoor and outdoor climate. To support room dehumidification, a ventilation fan can be directly connected and controlled via the Aero_aH 100.
Properties
- Power supply : 230V~ 50Hz
- power consumption : 8 W
- Protection class : IPX4
- flow rate : 78 m³/h bis zu 92 m³/h
- color : verkehrsweiß, ähnlich RAL 9016
- Material : Kunststoff
- Noise level : 27 dB(A) / 32 dB(A)
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100% rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
ViscoScope® VA-300
Maintenance-free inline process viscometer for real-time viscosity measurement
The ViscoScope® sensors are made of high-quality, first-class stainless steel and impress with their intelligent, robust design.
Properties
- Protection class : IP65
- Material : 1.4571 / 1.4404 (316Ti / 316L)
- Process temperature : -40°C … +450°C
- Process pressure : Vakuum ... 450 bar
- Process connections : DIN Flansch | ANSI Flansch | NPT | Varivent® | Tri-Clamp
- Cable length sensor - transmitter : max. 1.000m
- max. flow velocity : 10 m / sec
- Ex approval : (optional) II 1/2G Ex ia IIC T6...T3 Ga/Gb
- Material (optional) : Hastelloy C22, Duplex 2205, Teflon
Sensor types
- big cylinder : VA-300L
- small cylinder : VA-300M
- Sphere : VA-300H
- small sphere : VA-300X
Measuring range
- VA-300L : 0,1 - 2.500 mPa·s x g/cm³
- VA-300M : 1 - 25.000 mPa·s x g/cm³
- VA-300H : 0,01...250 Pa·s x g/cm³
- VA-300X : 0,1...2.500 Pa·s x g/cm³
Probe dimensions
- VA-300L : Ø 32 x 190 mm
- VA-300M : Ø 32 x 165 mm
- VA-300H : Ø 32 x 130 mm
- VA-300X : Ø 19 x 115 mm
ZS-1
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
Pressure measuring range
- 0...0,25mbar :
- 0...0,5mbar :
- 0...1mbar :
- 0...2,5mbar :
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (oponal)
- Overpressure : 1,2* (1,5*) x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
- Pressure range : 5…1.000 bar
Operating conditions
- Operating voltage : 14...28 VDC ± 10 %
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : G1/4" (andere auf Anfrage)
T-200.L 230V
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!