T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
16
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 120 °C
Operating pressure
:
max. 3 bar
media density
:
0,79 g/cm³
Resolution (depending on type)
:
7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
T20x.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
EE-2X
electrode, multiple for Ex-Zone 0 (Cat. 1)
The conductive electrodes of the EE-21/EE-22 series enable the monitoring of conductive liquids within the Ex area Zone 0 (Cat. 1).
Variants
cable connection on side
:
EE-21
cable connection on top
:
EE-22
Properties
connection
:
Edelstahl (1.4571)
Protection class EN60529
:
IP65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
electrode rods
:
Edelstahl (1.4571) | Hastelloy C | Tantal
Coating
:
PTFE
Operating temperature
Category 1 Class T6...T1
:
60 °C
Category 2 Class T6
:
80 °C
Category 2 Class T5
:
95 °C
Category 2 Class T4
:
130 °C (100°C)
Category 2 Class T3...T1
:
150 °C (100°C)
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
Connection aluminium box
:
H30 x B50 x T45 mm
Connection polyester box
:
H56 x B80 x T75 mm
connection cable
:
1000 mm PUR blau
Protection class Socket
:
IP65
Material Sliding tube
:
VA 1.4571
Material of the angle fastening
:
VA 1.4408
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm
Mounting
:
2 Schlauchschellen
Accessories
:
R/I-Wandler TK-101
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Our application engineers advise you