Cart
T-200.L Ex configure
XR-4x0 | XR-4x1 configure
T-20x.F 230V configure
Ex-QFS-3x configure
ZT-F configure
TK-313 configure
TK-307-0 configure
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80°C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
Ex-QFS-3x
Mercury-free float switches with Ex approval
These float switches have a mercury-free switching system consisting of a microswitch and a ball which actuates this switch.
Technical Data
- Protection class EN60529 : IP 68
- Material Float : PP
- Cable : TPK (PVC Basis), PVC Basis verstärkt, Polyurethan, Silikon, Teflon, Ethylen-Acrylat-Kautschuk
- Conductor cross-section : 3x 0,75 mm², Polyurethan 3x 0,5 mm²
- Operating temperature TPK(V) : AEM Kabel max.+ 60 °C
- Operating temperature PUR cable : max.+ 70 °C
- Operating temperature SIL, FEP cable : max.+ 85 °C
- Operating pressure : max. 1 bar Zylinder| max. 2 bar Kugel
- Switching system : Mikroschalter
- Contact type : Wechsler, NO, NC
- Electrical connection data, Ex-protection : siehe EG-Prüfbescheinigung TüV 09 ATEX 555342
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- CE marking : siehe Konformitätserklärung
- Weight : ca. 200 g
Media density Ex-QFS-30
- TPK(V) cable : ρρ 0,85 g/cm³
- PUR cable : ρρ 0,95 g/cm³
- SIL cable : ρρ 0,90 g/cm³
- FEP cable : ρρ 0,95 g/cm³
- AEM Cable : ρρ 0,90 g/cm³
Media density Ex-QFS-31
- Sphere : ρρ 0,60 g/cm
Mounting position
- Ex-QFS-30 : waagerecht mit G1” Verschraubung, senkrecht mit Beschwerungsgewicht (Ex)
- Ex-QFS-31 : waagerecht mit Flansch ab DN 100 (PP)
ZT-F
Reliable OEM pressure sensor with many customisation options (0...0,6 to 0…1.000 bar)
Can be used with all media and applications compatible with stainless steel
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
TPS-410 TPS-420
Compact, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
- Protection class : Gehäuse IP66, Stecker IP 67
- Weight : 96g
Properties TPS-420
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (dew point) : -50…+80 °C
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- Weight : ca. 150g
- ltdata. :
Power supply
- nominal voltage : siehe Typenschlüssel
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
- Switching delay : siehe Typenschlüssel
- Sensitivity range : siehe Typenschlüssel
Output
- Contacts : potentialfreie Wechselkontakte
- Switching voltage(min) : 5 V
- Switching voltage (max) : 250 V AC / 150 V DC
- Overvoltage category : EN 61010-1 Kategorie III
Switching current
- Switching current : min. 5 mA
- Switching current : max. cos φ =1 5 A
- Switching current : max. cos φ = 0,7 3 A/AC
- Switching current : max. cos φ = 1
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
- Connection aluminium box : H30 x B50 x T45 mm
- Connection polyester box : H56 x B80 x T75 mm
- connection cable : 1000 mm PUR blau
- Protection class Socket : IP65
- Material Sliding tube : VA 1.4571
- Material of the angle fastening : VA 1.4408
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
T209-0.F
Magnetic immersion probe overfill protection for Ex zone 0 (Cat. 1)
The magnetic immersion probes T20... are used to detect fill level limit values in containers for liquid media, where an explosive atmosphere of zone 0 (cat. 1) is present in the gas space above the liquid and Ex zone 1 (cat. 2) is present outside the container, in the area of the junction box.
Properties
- connection : Polyesterdose, Aluminiumdose
- Protection class : IP 65 Dose
- Float type : Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135°C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : 6x Wechsler, 9x Schließer, 6x Öffner
- Switching current : 1A, 2A ( nur mit Schirmung)
- Switching capacity : Wechsler: 60 W/VA, Schließer: 100 W/VA Öffner: 60 W/VA
- min. contact distance with several floats : 125 mm
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!