ES-21 configure
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
Aero_aH100
Exhaust air fan with integrated dehumidification control for automatic room dehumidification
Dehumidification control, including integrated indoor and outdoor climate sensor. Controlled dehumidification takes place by comparing the indoor and outdoor climate. To support room dehumidification, a ventilation fan can be directly connected and controlled via the Aero_aH 100.
Properties
- Power supply : 230V~ 50Hz
- power consumption : 8 W
- Protection class : IPX4
- flow rate : 78 m³/h bis zu 92 m³/h
- color : verkehrsweiß, ähnlich RAL 9016
- Material : Kunststoff
- Noise level : 27 dB(A) / 32 dB(A)
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100% rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
T205-0
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 68 Kabel
- Float type : max. 4x Zylinder Edelstahl 27 mm Ø
- connection cable : 1000 mm PUR Blau
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 120 °C
- Operating pressure : max. 10 bar (Schwimmer)
- media density : 0,78 g/cm³
- Number of contacts : max. 2 Schließer / 2 Öffner
- Switching current : 1A, 2A
- Switching capacity : 50 W/VA
- min. contact distance with several floats : 50 mm
ZS-Serie
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
ES-21
Electronic safety switching device with 1 safety function
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
Our application engineers advise you personally, comprehensively and professionally!