Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
PO/ET-520
ltdata.Polyethylenanschlusskopf
:
PE/ET-521
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
max. 80 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24 V DC (24…300V DC)
Power consumption
:
≤ 1 W
Output
Output contact
:
1 potentialfreier Wechselkontakt
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 3 A AC / 3 A DC
Switching capacity
:
max. 750 VA / 90 W
Optocoupler
Switching voltage
:
max. 30 V
Switching current
:
max. 100 mA
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
connection
:
integrierter Anschlusskopf
Protection class
:
IP 65
connection thread
:
G 1¼"
Material Screw connection
:
PPH
Material electrode rods
:
Edelstahl (1.4571), Hastelloy C, Titan, Tantal
material coating
:
PTFE
Coating length
:
voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
Rod diameter
:
4 mm, 6 mm
rod length
:
max. 6 m
Operating temperature
:
85 °C
Operating pressure
:
atmosphärisch
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
Operating temperature
:
–20...+85 °C
Storage temperature
:
–30...+85 °C
nominal voltage
:
24 V DC ± 15%
Power consumption
:
max. 2 W (Klemme A1, A2)
Switching voltage
:
max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
Switching current
:
max. 3 A AC, 3 A DC min. 1 mA
Switching capacity
:
max. 750 VA, 150 W
Sensitivity
:
3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties