EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Box : Polyethylen-Anschlusskopf (PE)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
KST-20 Vento-RN
Climate control with aH-Controlled technology and Rn-Protected seal
The KST-20 Vento/RN is a climate control unit with aH-Controlled technology and Rn-Protected seal for ventilation and dehumidification of all types of private, commercial and industrial rooms. With the three operating modes for ventilation, dehumidification and radon measurement, the KST-20 Vento climate control unit can be used flexibly in almost all living, working and industrial areas.
Properties
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertigem ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100 % rF
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- measuring range (radon) : 0...1200 Bq/m³
- Adjustable limits : 80...1000 Bq/m³
KS-410 KS-420
Sensors for temperature & humidity measurement in aluminium or polycarbonate housing
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
- Housing shapes : Stabform | Alu- oder Polycarbonatgehäuse
- measurands : Temperatur | relative Feuchte
- Measuring range : -40...+80 °C | 0...100% rH
- Signal output : 0...10 V oder 4…20 mA
- Power supply : 12...30 V DC | 24 V DC
properties KG-410
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
properties KG-420
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Alu-Gehäuse mit Edelstahlstab oder Polycarbonat
- Dimensions (LxBxH in mm) : 30 x 45,4 x 97,3
- Protection type/class : Gehäuse IP66, Stecker IP 67
- Weight : 96g
Measuring range
- measuring range (Humidity) : 0…10% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
- TK-320 : Schaltschrankeinbaugehäuse 24 x 96 mm
- TK-321 : Schaltschrankeinbaugehäuse 24 x 96 mm
- TK-322 : 19” Karteneinschub 7 TE, 3 HE
Properties
- Protection class EN60529 : IP 52
- Operating temperature : – 20 °C...+60 °C
- nominal voltage : 24 V DC...230 V AC
- Input : 0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
- Output : 4...20 mA | Bürde max. 500 Ω
- Relay : 2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
- Number of LEDs : 33 (rot/grün); 32 (TK-322)
- Resolution : ca. 3,5 %
- Error : ± 1 LED
- connection : Schraubklemmen
- connection TK-322 : Steckerleiste
- Input : 0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
- Output : 4...20 mA | max. load 500 Ω
- Relay(2xSwitch) : max. 230 V | min. 5 V
- Relay(2xSwitch) : max. 3 A | min. 1 mA
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties KS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…10% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
TK-307
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Connection housing : Aluminium H 30 mm x B 50 mm x T 45 mm
- Connection socket : Polyester H 55 mm x B 80 mm x T 45 mm
- Protection class socket / plug : IP 65
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution depending on type : 7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
- measuring range (Humidity) : 0…100 % rF,
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- Signal output : I2C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000…1.500 ppm
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
- measuring range (Humidity) : 0...100 % rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80 °C
- Measuring accuracy (temperature) : ± 0,2 °C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000...1.500 ppm
ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm
Product features
- Measuring principle : optisch, NDIR (nicht-dispersive Infrarot-Absorptionsmessung)
- Operating voltage : 24 V DC / 100 mA
- Heating time : ca. 5 min
- Response time : ca. 30 s
- Repeatability : +/- 1%
- Housing : Aluminium (rot) IP54
- Weight : ca. 500g
- Shaft range : 4,27 - 4,35 µm (4270-4350 nm)
- Gas ingress : per Diffusion
ambient conditions
- Operating temperature range : -10...+50 °C
- Storage temperature range : -40...+100 °C
- RelativeHumidity : 15..95 %
- Air pressure : 900...1100 hPa
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
T204
Magnetic immersion probe made of stainless steel (1.4571)
For use with highly aggressive liquid media to detect level limit values in containers. Suitable for use in hazardous areas, zone 0 (category 1).
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- connection thread : G1 1/2" | G2"
- Sliding tube length : max. 6000 mm (Rohr Ø 12 mm)
- Operating pressure : max. 20 bar (Kugel) | max. 15 bar (Zylinder)
- Operating temperature : max. 135 °C
- Number of floats : max. 4
Float type
- Stainless steel ball 52mm ⌀ : Dichte: 0,75 g/cm³ | mind. Kontaktabstand: 75 mm
- Stainless steel ball 62mm ⌀ : Dichte: 0,65 g/cm³ | mind. Kontaktabstand: 85 mm
- Stainless steel cylinder 44 mm Ø : Dichte: 0,76 g/cm³ | mind. Kontaktabstand: 75 mm
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 4
- normally open : 6
- Normally closed contact : 4
EF2X
Double pipe and filling pipe monitoring
EF2L and EF2T -conductive-
with general technical approval for construction Z-65.13-405
Properties
- Electrical connection : Stecker GDM
- Protection class EN60529 : IP 65 mit Dichtung
- connection : PVC Überwurfmutter G 1 ¼“
- PVC : max. +60 °C
- PE : max. +80 °C
- Storage temperature : -30...+85 °C
- Operating pressure : max. 6 bar
Material
- Pipe : PVC | PE
- Sensor rods : Edelstahl 1.4571 | Hastelloy B/C | Titan | Tantal
tdata.ElektronikteilET-473L|ET-473T
- nominal voltage : 20...30 V DC
- Power consumption : 1 VA
- Output contact : Schließer | Öffnerkontakt (NO/NC) (nicht potentialfrei)
- Switching voltage : 12...30 V DC
- Switching current : max. 300 mA
- Switching capacity : max. 9 W
- Sensitivity range : 2...30 kOhm
- ltdata. :
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- Weight : ca. 150g
- ltdata. :
Power supply
- nominal voltage : siehe Typenschlüssel
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
- Switching delay : siehe Typenschlüssel
- Sensitivity range : siehe Typenschlüssel
Output
- Contacts : potentialfreie Wechselkontakte
- Switching voltage(min) : 5 V
- Switching voltage (max) : 250 V AC / 150 V DC
- Overvoltage category : EN 61010-1 Kategorie III
Switching current
- Switching current : min. 5 mA
- Switching current : max. cos φ =1 5 A
- Switching current : max. cos φ = 0,7 3 A/AC
- Switching current : max. cos φ = 1
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties TPS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…100% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -50...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
TK-315
Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99 mm
- Dimensions housing type C : 22,5 x 114,5 x 114 mm
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 4 Schließerkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
Our application engineers advise you personally, comprehensively and professionally!