Cart
EFV2 24V configure
QFS-3X configure
Fluidix Lub-VDT configure
ELH 230 V configure
BK-380 configure
ESE configure
EFV2 24V
adaptive conductive electrodes with and without 24 V direct connection
The conductive electrode EFV2 is approved by the "DIBt" as an overfill prevention device for liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾", S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal, Kohlestifte
- Operating temperature : PE, PVC: atmosphärisch PPH : 90 °C, PVDF: 100 °C
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ je nach Ausführung
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Technical specifications electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24...30 V DC
- Power consumption : max. 2 W
- Switching voltage : max. 230 V AC / V DC min. 5 V DC (CMOS-Relais)
- Switching current : max. 0,12 A AC / A DC min. <1 mA
- Switching capacity : max. 25 VA / W
- Sensitivity : 3k … 100 kΩ
QFS-3X
Mercury-free float switch with µ-switch
Properties
- Protection class EN60529 : IP 68
- Cable entry : PVC , PTFE bzw. PVDF
- Conductor cross-section : 3 x 0,75 mm², PUR 3x 0,5mm²
- Operating pressure cylinder : max. 1 bar
- Operating pressure sphere : max. 2 bar
- Switching system : µ-Schalter
- Contact : Wechsler, NO, NC
Material Float
- QFS-30 : PPH (Polypropylen)
- QFS-31 : PPH (Polypropylen)
- QFS-34 : PE (Polyethylen)
Cable
- TPK : PVC Basis Ø 5,9 mm
- TPKV : PVC verstärkt Ø 7,3 mm
- PUR : Polyurethan Ø 5,4 mm
- SIL : Silikon Ø 6,4 mm
- FEP : Teflon Ø 4,0 mm
- AEM : Ethylen-Acrylat-Kautschuk
Cable length between float & attachment
- TPK : 70 mm
- TPKV : 90mm
- PUR : 100mm
- SIL : 80 mm
- FEP : 110 mm
- AEM : abhängig vom Innenkabel
Operating temperature
- TPK(V), AEM : max. + 60 °C
- PUR : max. + 70 °C
- Silicone,Tefloncable with PE float : max. + 80 °C
- Silicone, Teflon cable with PP float : max. + 85 °C
MaterialDensity
- QFS-31 : ≥≥ 0,6 g/cm³
- QFS-34 : ≥≥ 0,75 g/cm³
- QFS-30 TPK(V) cable : ≥≥ 0,85 g/vcm³
- QFS-30 PUR cable : ≥≥ 0,95 g/cm³
- QFS-30 SIL cable : ≥≥ 0,90 g/cm³
- QFS-30 FEP cable : ≥≥ 0,95 g/cm³
- QFS-30AEM cable : ≥≥ 0,90 g/cm³
Fluidix Lub-VDT
Oil condition sensor for permanent monitoring of mechanical properties of liquids
The FluidIX Lub-VDT enables inline monitoring of mechanical fluid properties.
Properties
- CE marking : EN 61000-6-1/2/3/4
- Operating voltage : 9...32 V DC
- Housing material : Edelstahl
- Protection class : IP 67
- Dimensions : 30x90 mm
- Process connection : G 3/8"
- Electrical connection : M12-8 A-Coding
- Weight : 150g
- Measurement output : 2x 4...20mA
- bus protocol : ModbusRTU, CANopen
Measured variables
- Resonator frequency : 20...25 kHz
- Viscosity : 1-650 cSt (mm²/s)
- density : 0.5-1.5 g/cm³
- Temperature : -40...+125°C
- sampling rate : 1/s
Operating conditions
- Temperature of the fluid : -40...+125°C
- Housing temperature : -40...+100°C
- oil pressure : Max. 50 bar
- particle size : 250 μm
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (oponal)
- Overpressure : 1,2* (1,5*) x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
- Pressure range : 5…1.000 bar
Operating conditions
- Operating voltage : 14...28 VDC ± 10 %
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : G1/4" (andere auf Anfrage)
T-20X
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
ELH 230 V
Hanging electrode as leakage probe 24...230 V AC/DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
BK-380
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
T205 PP
Magnetic immersion probes made of PP
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : 1x Typ 12 | 1x Typ 13
- connection cable : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : max. 60 °C
- Operating pressure : drucklos
- Number of contacts : 1x Schließer / Öffner
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
Float type
- Type 12 : Zylinder PP 19 mm Ø | Dichte 0,93 g/cm³
- Type 13 : Zylinder PP 25 mm Ø | 0,68 g/cm³
ESE
Switching channel extension for ES series
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
Our application engineers advise you personally, comprehensively and professionally!