Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
QFSK-2X
Stainless steel float switch combination
Float switch combinations QFSK for level monitoring & level control with maximum and minimum contact sensor.
Properties
Protection class EN60529
:
IP 68
Material Float
:
VA 1.4571
Material hose
:
Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
rod length
:
max. 5 m
Number of floats
:
bis 5
Operating temperature
:
max. + 150 °C
media density
:
ρ ≥ 0,8g/cm³
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Ex-protection
:
optional; IBExU10ATEX 1089
Operating pressure WFSK-25
:
max. 15 bar
Operating pressure QFSK-26
:
max. 6 bar
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
Temperature:
:
-40...80°C
rel. Humidity
:
0 - 100% rH
Measuring range
measuring range (dew point)
:
-50...+80°C
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V oder 4...20mA
NSP-X-E
Vibrating Limit Switch
The vibrating limit switch is a level limit switch for all kinds of fluids and is used in tanks, containers and pipelines.
Properties
Protection class EN60529
:
IP 65/IP 67
Operating pressure
:
≤ 40 bar
media density
:
ρ ≥ 0,7 g/cm³
Viscosity
:
max. 10000 mm²s
Rated current
:
< 15 mA
Protection class
:
III
Output
:
PNP
power
:
kurzschlussfest, überlastsicher
Display
:
LED (grün, rot)
Switching delay (cover)
:
ca. 0,5 s
Switching delay (release)
:
ca. 1 s
NSP-1-E
connection thread
:
G 1”
Operating temperature
:
–40...+150 °C
Storage temperature
:
–40...+85 °C
nominal voltage
:
10...55 V DC (verpolsicher)
Current output
:
≤ 350 mA
NSP-2-E
connection thread
:
G ½”
Operating temperature
:
–40...+100 °C
Storage temperature
:
–20...+70 °C
nominal voltage
:
10...35 V DC (verpolsicher)
Current output
:
≤ 250 mA
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
Weight
:
ca. 150g
ltdata.
:
Power supply
nominal voltage
:
siehe Typenschlüssel
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Switching delay
:
siehe Typenschlüssel
Sensitivity range
:
siehe Typenschlüssel
Output
Contacts
:
potentialfreie Wechselkontakte
Switching voltage(min)
:
5 V
Switching voltage (max)
:
250 V AC / 150 V DC
Overvoltage category
:
EN 61010-1 Kategorie III
Switching current
Switching current
:
min. 5 mA
Switching current
:
max. cos φ =1 5 A
Switching current
:
max. cos φ = 0,7 3 A/AC
Switching current
:
max. cos φ = 1
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
details
:
folgen
EP
Plate Electrode as Leak Detector (conductive)
with general approval for constructions and EC-Type-Examination Certificate for Ex-zone 1(Cat. 2)
Properties
Protection class EN60529
:
IP 68
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
cable length
:
auf Wunsch
Material
Cable
:
TPK (PVC Basis)
Sensor rods
:
Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
cable material
:
FEP (Teflon) | EX (PVC blau)
ZMF-202e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
Operating conditions
:
-40 °C…+60 °C
Storage conditions
:
-40 °C…+85 °C
RelativeHumidity
:
0…95 % nicht kondensierend
Measurement method
:
NDIR (dual beam technology)
Certification
:
SIL2, ATEX
Signal output
:
4..20mA
Power supply
:
12…24 V DC
Housing
:
Edelstahl
Standard cable length
:
1,5 m
pressure conditions
:
800...1200 mbar
screw thread
:
M46x1,5
Measuring ranges
in ppm
:
in vol%
0...17.000ppm
:
0…1,7 vol% (100 % LEL)
0...21.000ppm
:
0…2,1 vol%
Options
Other cable lengths on request
:
ATEX certification (optional)
:
Our application engineers advise you