Cart
QFS-55 configure
KG-2XX configure
LU-1X0 configure
NP-256 configure
EF2…5 24V configure
PVS-390 configure
ELH 24 V configure
EP configure
QFS-55
Teflon float switch in rod design
The float switch combination is built with float switches of the QFS-50 and QFS-60 series. This makes it possible to control a level in a simple way.
Technical Data
- Material : PTFE (Teflon)
- connection cable : Silikon, Teflon
- Material rod : VA-Rohr, PTFE beschichtet
- Operating temperature : max. +150 °C
- media density : ρ ≥ 0,75 g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- Ex-protection optional : Elektrische Daten siehe EG-Prüfbescheinigung IBExU10ATEX 1089
Reed contact
- Switching current : 1 mA ... 1 A
- Switching voltage : 24 ... 250 V AC/DC
- Switching capacity : Max. 1A, 60 VA / 60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Namur circuit (1kΩ/12kQ)
- Switching current / switching voltage : nur zum Anschluss an KR-163... oder andere „Namur”-Relais
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
NP-256
Level Switch - multiple 2...4 - pneumatic (hose)
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
- Protection class EN60529 : IP 54
- connection thread : ab G2”
- Union nut : ab G2¾”
- Container connection flange : ab DN 25
- HoseØ : 13x2 mm
- Operating temperature : +60 °C
- medium temperatur : max. +60 °C
- Contact : Wechsler
- Switching capacity : 500 VA
- Switch-on point (Viton membrane) : 150 mm WS ±30 mm
- Switch-off point (MembraneViton) : 90 mm WS ±30 mm
Material
- Hose : PVC
- Screw fitting/grommet : PVC
- flange : PVC
- Connection head : PVC
Switching voltage
- silver : max. 250 V AC
- Gold : max. 24 V AC
Switching current
- silver : max. 6 A
- Gold : max. 100 mA
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
- 40 : AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
- 50 : AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
ELH 24 V
Hanging electrode as leakage probe 24 V DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
T209
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
CS-11
CO2 Sensor with digital Interface
Digital CO2 sensor CS-11 for measuring carbon dioxide concentration in mobile applications.
Properties CS-11
- Measured variable: : CO2
- Measuring range: : 0…5.000 ppm
- Measuring principle: : optisch, NDIR
- Housing : Kunststoff
- measuring grid : 2 sec.
- Accuracy : ± 50 ppm
- Protocol : I²C-Bus
- Operating conditions Temperature : -0°C … 50°C
- Operating conditions Humidity : 0…85 % rH
- Storage conditions Temperature : -30°C … 70 °C
- Storage conditions Humidity : 0…85 % rH
Properties MV-CAN
- Housing : Plastik
- Mounting : Hutschienenmodul für Einbau in Schaltschrank
- Operating voltage : 10…48 V
- measuring grid : 2 sec.
- CAN protocol : CANopen 2.0 A nach CiA DS 404
- Physical Layer : nach ISO 11898
- Option : Bereitstellung des EDS-Files
- Operating temperature : -40°C … +80°C
- Storage temperature : -40°C … +120 °C
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
EP
Plate Electrode as Leak Detector (conductive)
with general approval for constructions and EC-Type-Examination Certificate for Ex-zone 1(Cat. 2)
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!