Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
details
:
folgen
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Ex-Polyester
Box
:
Ex-Aluminium
Properties
Protection class EN60529
:
IP 65
connection thread
:
G2"
Union nut
:
G 2¾"
Guide tube length
:
max. 6 m
Operating temperature
:
-20…+60 °C
Operating pressure
:
max. 6 bar je nach Ausführung
media density
:
ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
Ex-protection
:
siehe Baumusterprüfbescheinigung
CE marking
:
siehe Konformitätserklärung
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
Weight
:
ca. 150g
ltdata.
:
Power supply
nominal voltage
:
siehe Typenschlüssel
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Switching delay
:
siehe Typenschlüssel
Sensitivity range
:
siehe Typenschlüssel
Output
Contacts
:
potentialfreie Wechselkontakte
Switching voltage(min)
:
5 V
Switching voltage (max)
:
250 V AC / 150 V DC
Overvoltage category
:
EN 61010-1 Kategorie III
Switching current
Switching current
:
min. 5 mA
Switching current
:
max. cos φ =1 5 A
Switching current
:
max. cos φ = 0,7 3 A/AC
Switching current
:
max. cos φ = 1
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties TPS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…100% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-50...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
KS-410 KS-420
Sensors for temperature & humidity measurement in aluminium or polycarbonate housing
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
Housing shapes
:
Stabform | Alu- oder Polycarbonatgehäuse
measurands
:
Temperatur | relative Feuchte
Measuring range
:
-40...+80 °C | 0...100% rH
Signal output
:
0...10 V oder 4…20 mA
Power supply
:
12...30 V DC | 24 V DC
properties KG-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
properties KG-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Alu-Gehäuse mit Edelstahlstab oder Polycarbonat
Dimensions (LxBxH in mm)
:
30 x 45,4 x 97,3
Protection type/class
:
Gehäuse IP66, Stecker IP 67
Weight
:
96g
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
NP-255
Level Switch - multiple 2...4 - pneumatic
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
Protection class EN60529
:
IP 54
connection thread
:
ab G2”
Union nut
:
ab G2¾”
Container connection flange
:
ab DN 25
Hose Ø
:
16 mm
Operating temperature
:
+60 °C
medium temperatur
:
max. +60 °C
Contact
:
Wechsler
Switching capacity
:
500 VA
Switch-on point (Viton membrane)
:
150 mm WS ±30 mm
Switch-off point (MembraneViton)
:
90 mm WS ±30 mm
Material
Pitot tube / Hose
:
PVC
Screw fitting/grommet
:
PVC
flange
:
PVC
Connection head
:
PVC
Switching voltage
silver
:
max. 250 V AC
Gold
:
max. 24 V AC
Switching current
silver
:
max. 6 A
Gold
:
max. 100 mA
TK-301 PTFE
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
16
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 120 °C
Operating pressure
:
max. 3 bar
media density
:
0,79 g/cm³
Resolution (depending on type)
:
7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
Our application engineers advise you
personally, comprehensively and professionally!