Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Polyester junction box
:
Aluminum housing
:
Polyethylene connection head
:
Cable
:
Plug
:
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Operating temperature
:
atmosphärisch
PP
:
max. 90°C
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
QFS-12
Two-Point Float-Switch
With the two-point float switch Type QFS-12 can be realized pump controls in liquid media on a simple way.
Properties
Protection class EN60529
:
IP68
Side installation
:
PVC-Stopfbuchsverschraubung G 2”
Installation from above
:
PVC-Stopfbuchsverschraubung G 2”
Operating pressure
:
max. 2 bar
Contact
:
Wechselkontakt
Switching voltage
:
4....250 V AC / DC
Switching current
:
1mA.....1A
Switching capacity
:
60W/VA
media density
:
ρ ≥ 0,9 g/cm³ bis ρ ≥ 0,8 g/cm³
Material Float
:
Polyethylen
Cable
TPK
:
PVC Basis
TPKV
:
PVC Basis verstärkt
PUR
:
Polyurethan
NEO
:
Neopren
SIL
:
Silikon
FEP
:
Teflon
AEM
:
Ethylen-Acrylat-Kautschuk
Operating temperature
TPK(V), NEO, AEM
:
max.+60 °C
PUR
:
max.+70 °C
FEP, SIL
:
max.+80 °C
ViscoScope® VA-100
Inline Viscometer
Maintenance-free inline viscosity sensor for precise and reliable real-time measurement of viscosity directly in the process.
Properties
Material
:
1.4571 / 1.4404 (316Ti / 316L)
Protection class
:
IP65
Process temperature
:
-10°C … +130°C | (integriertes Pt100 im Messfühler)
max. process pressure
:
Vakuum ... 64 bar
Process connections
:
NPT | M48 | Varivent® | Tri-Clamp
Cable length sensor - transmitter
:
Max. 1.000 Meter
max. flow velocity
:
5 m / sec
Ex approval
:
II 1/2G Ex ia IIC T6...T3 Ga/Gb | (optional)
Sensor types
Sphere
:
VA-100B
Cylinder
:
VA-100C
Repeatability
VA-100B
:
± 0,5% | ± 1 Digit
VA-100C
:
± 0,3% | ±1 Digit
Measuring ranges
VA-100C
:
0,1 - 2.500 mPa·s x g/cm³
VA-100B
:
10 - 25.000 mPa·s x g/cm³
Probe dimensions
VA-100C
:
Ø 32 x 145 mm
VA-100B
:
Ø 32 x 120 mm
installation positions
Reservoir
:
tanks
:
Pipe
:
flow cell
:
Installation is position-independent
:
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
Housing
:
Aluminium
Protection class
:
IP30
Dimensions
:
197 x 153 x 37,5mm (B x H x T)
Temperature range
:
0 – 50°C
Supply voltage
:
24V DC +/-20%
Power consumption
:
120mA – 220mA
Reverse polarity protection
:
✓
Display
:
4x20
Outputs
analog 0(4)–20mA
:
3x
digital
:
4x
fixed for alarm
:
1x
free configurable
:
3x
display of measured value
Flow velocity
:
Filling level
:
flow
:
flow rate
:
MO
Monostable Switch
Properties
Protection class
:
IP 65
Switching current
:
max. 1 A
Switching voltage
:
max. 24 V
Switching capacity
:
max. 20 W/VA
Material
Housing
:
Messingrohr Ø 10 x 1
Cable
:
TPK (PVC basis) | SIL (Silikon)
Operating temperature
TKP
:
–15 ° ... + 60 °C
SIL
:
–15 ° ... +130 °C
Our application engineers advise you
personally, comprehensively and professionally!