Cart
product added to request
T-200.L Ex configure
Ex-QFS-3x configure
VS-D250 configure
NP-256 configure
QFS-40 configure
XR Relais configure
PVS-390 configure
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
- Measuring range : -40…+80 °C
- deviation : ± 0,3 K (10...80 °C)
- Measuring element : Halbleiter-Diodenfühler
- measuring resolution : 0,1 K
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 10...48 V
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
- Minimumairspeedrequiredformeasurementacrossthesensor : 1,5 m/s
Ex-QFS-3x
Mercury-free float switches with Ex approval
These float switches have a mercury-free switching system consisting of a microswitch and a ball which actuates this switch.
Technical Data
- Protection class EN60529 : IP 68
- Material Float : PP
- Cable : TPK (PVC Basis), PVC Basis verstärkt, Polyurethan, Silikon, Teflon, Ethylen-Acrylat-Kautschuk
- Conductor cross-section : 3x 0,75 mm², Polyurethan 3x 0,5 mm²
- Operating temperature TPK(V) : AEM Kabel max.+ 60 °C
- Operating temperature PUR cable : max.+ 70 °C
- Operating temperature SIL, FEP cable : max.+ 85 °C
- Operating pressure : max. 1 bar Zylinder| max. 2 bar Kugel
- Switching system : Mikroschalter
- Contact type : Wechsler, NO, NC
- Electrical connection data, Ex-protection : siehe EG-Prüfbescheinigung TüV 09 ATEX 555342
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- CE marking : siehe Konformitätserklärung
- Weight : ca. 200 g
Media density Ex-QFS-30
- TPK(V) cable : ρρ 0,85 g/cm³
- PUR cable : ρρ 0,95 g/cm³
- SIL cable : ρρ 0,90 g/cm³
- FEP cable : ρρ 0,95 g/cm³
- AEM Cable : ρρ 0,90 g/cm³
Media density Ex-QFS-31
- Sphere : ρρ 0,60 g/cm
Mounting position
- Ex-QFS-30 : waagerecht mit G1” Verschraubung, senkrecht mit Beschwerungsgewicht (Ex)
- Ex-QFS-31 : waagerecht mit Flansch ab DN 100 (PP)
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
- Housing : Kunststoff
- Power supply 24V : 24V DC | 230V
Measuring element and parameter
- Measuring principle : optisch, NDIR
- measuring grid : 2 sec.
- Accuracy : ± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
Operating conditions
- Operating temperature : 0…+50 °C
- Storage temperature : -30 °C…+75 °C
- Operating humidity : 0…85% rH (nicht kondensierend)
- Storage humidity : 0…85% rH (nicht kondensierend)
VS-D250
Transmitter for ViscoScope viscosity sensors
Maximum flexibility for an optimal choice of measuring instrument: The VS-D250 transmitter is compatible with all ViscoScope® sensors of the types VA-100 and VA-300.
Properties
- Output card socket : 2
- External input : 0/4…20 mA | 0/2…10 V DC
- Power supply : 24V DC, 12 W
- Dimensions : 142 x 106 x 73 mm (L x B x H)
- Front : RS232, MODBUS RTU (Standard)
Display and Operation
- Lines : 4
- Pages : 2
- Character set : alphanumerisch
- Buttons : 3 (front)
Alarms
- system function :
- sensor diagnosis :
- Coil Temperature :
- 2 configurable LEDs :
optional outputs
- 0/4…20mA | 0/2…10V DC (active) :
- RS232 | RS485 :
- 2 SPDT-Relays: RS232 | RS485 :
Filter
- Moving average (200 measured values) :
TPS-410 TPS-420
Compact, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
- Protection class : Gehäuse IP66, Stecker IP 67
- Weight : 96g
Properties TPS-420
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (dew point) : -50…+80 °C
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
NP-256
Level Switch - multiple 2...4 - pneumatic (hose)
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
- Protection class EN60529 : IP 54
- connection thread : ab G2”
- Union nut : ab G2¾”
- Container connection flange : ab DN 25
- HoseØ : 13x2 mm
- Operating temperature : +60 °C
- medium temperatur : max. +60 °C
- Contact : Wechsler
- Switching capacity : 500 VA
- Switch-on point (Viton membrane) : 150 mm WS ±30 mm
- Switch-off point (MembraneViton) : 90 mm WS ±30 mm
Material
- Hose : PVC
- Screw fitting/grommet : PVC
- flange : PVC
- Connection head : PVC
Switching voltage
- silver : max. 250 V AC
- Gold : max. 24 V AC
Switching current
- silver : max. 6 A
- Gold : max. 100 mA
QFS-40
Built-in float level switch
The QFS-40 built-in float switch is designed for low-cost monitoring of liquids in containers.
Technical Data
- Switch housing : PPH| PVDF
- Seal : NBR (PPH) | FPM (PVDF)
- Operating temperature : PPH max. 80 °C| PVDF max. 100 °C
- Operating pressure : max. 10 bar
- Mounting position : horizontal (±30° von der Horizontalen)
- Contact assembly : Schliesser-, Öffnerkontakt (je nach Einbau)
- Electrical connection : PVC-Kabel
- Switching capacity : max. 230 V AC/DC| max. 40 VA, max. 2 A
- Contact resistance : max. 80 mW
- Min. electric strength : 400 V DC / 1 s
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- fluid density : PPH > 0,6 kg/dm³ | PVDF > 0,95 kg/dm³
- Protection class : IP 68
Connections
- external installation : G ½"
- internal installation : M16
XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Weight : ca. 170g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
- 40 : AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
- 50 : AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!