Cart
ZMF-100-IR configure
ZT-V configure
LU-180 EX configure
PVG-399 configure
AD-310 configure
ZT-S configure
TK-313 configure
T203 configure
QFS-55 configure
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
T204-0
Magnetic immersion probe made of stainless steel (1.4571) as a cable tail variant
For use with highly aggressive liquid media to detect level limit values in containers. Suitable for use in hazardous areas, zone 0 (category 1).
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm
Product features
- Measuring principle : optisch, NDIR (nicht-dispersive Infrarot-Absorptionsmessung)
- Operating voltage : 24 V DC / 100 mA
- Heating time : ca. 5 min
- Response time : ca. 30 s
- Repeatability : +/- 1%
- Housing : Aluminium (rot) IP54
- Weight : ca. 500g
- Shaft range : 4,27 - 4,35 µm (4270-4350 nm)
- Gas ingress : per Diffusion
ambient conditions
- Operating temperature range : -10...+50 °C
- Storage temperature range : -40...+100 °C
- RelativeHumidity : 15..95 %
- Air pressure : 900...1100 hPa
ZT-V
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Connection
- Signal output : 0...10 V, 3-Leiter | 0,5...4,5, ratiometrisch | 4...20 mA, 2-Leiter
- Electrical connection : DIN EN 175301-803 A | DIN EN 175301-803 C | Binder M12x1 (Serie 713)
- Process connection : G 1/4" ISO 1179-2 (Male Form E) | 1/4" NPT | 7/16" 20 UNF Male
- measuring range (bar) : 0…0,6 | 0…600
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40°C...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
LU-180 EX
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
ZT Serie
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
- Measuring range : -40…+80 °C
- deviation : ± 0,3 K (10...80 °C)
- Measuring element : Halbleiter-Diodenfühler
- measuring resolution : 0,1 K
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 10...48 V
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
- Minimumairspeedrequiredformeasurementacrossthesensor : 1,5 m/s
PVG-399
PVC weight with magnet insert and eyelet for cable fixing
for actuating monostable and bistable contacts
Variants
- 32 : Außen Ø 25 mm x 175 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 32 u. 34 mm bis 6m Länge
- 37 : Außen Ø 30 mm x 170 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 40 mm bis 6m Länge
- 40 : Außen Ø 40 mm x 110 mm ca. 175g, geeignet für Rohraußen Ø 50 mm bis 6m Länge
- 4012 : Außen Ø 40 mm x 110 mm ca. 300g, geeignet für Rohraußen Ø 50 mm bis 12m Länge
- 4016 : Außen Ø 40 mm x 110 mm ca. 360g geeignet für Rohraußen Ø 50 mm bis 16m Länge
- 50 : Außen Ø 50 mm x 130 mm ca. 255g, geeignet für Rohraußen Ø 63 mm bis 6m Länge
- 5012 : Außen Ø 50 mm x 130 mm ca. 300g geeignet für Rohraußen Ø 63 mm bis 12m Länge
- 5016 : Außen Ø 50 mm x 130 mm, ca. 360g, geeignet für Rohraußen Ø 63 mm bis 16m Länge
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel : IP 65
- Operating temperature : – 20...+ 60 °C
- nominal voltage : Weitbereichsnetzteil; 20 V DC ... 230 V AC
- Power consumption : max. ca. 3 VA
- Output contact : 2 Schließer / NO
- Switching voltage : max. 250 V AC, 300 V DC
- Switching current : max. 3 A , DC min. 30 mA
- Switching capacity : max. 50W, 100 VA
- Unregulated auxiliary voltage source : 15...20 V DC / 20 mA
- Display : LED 14 mm, 5-stellig
- Dimensions : 96x48x100 mm
- Weight : ca. 200 g
- Panel cut-out : H:45+0,6mm, B:92+0,8 mm
Equipment
- Measuring input current : 0(4)...20 mA DC
- Measuring input voltage : 0(2)...10 V DC
- Measuring input Potentiometric voltage divider : 1...100 kΩ
- Display : LED 14 mm, 5-stellig
- operation : Folientasten
- Display range : -19999...32000
- data backup : EEPROM
- measurement uncertainty : ±1 % oder ±1 Digit
- analogue output : 0 (4)...20 mA
KS-Serie
Sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
- Housing shapes : Stabform | Alu- oder Polycarbonatgehäuse
- measurands : Temperatur | relative Feuchte
- Measuring range : -40...+80 °C | 0...100% rH
- Signal output : 0...10 V oder 4…20 mA
- Power supply : 12...30 V DC | 24 V DC
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- Measuring range nominal pressure : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- fluid temperature (optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- Standard : Binder M12 x 1
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
- Pressure range : 0...500mbar gestuft
- supply : 12 - 24 V DC
- Output : Relais 230 V/1A
- overload : 2 x Messbereich
- Med. connection : Schlauch
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
- Housing : Kunststoff
- Power supply 24V : 24V DC | 230V
Measuring element and parameter
- Measuring principle : optisch, NDIR
- measuring grid : 2 sec.
- Accuracy : ± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
Operating conditions
- Operating temperature : 0…+50 °C
- Storage temperature : -30 °C…+75 °C
- Operating humidity : 0…85% rH (nicht kondensierend)
- Storage humidity : 0…85% rH (nicht kondensierend)
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
T203
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
tdata.
- connection : Polyesterdose | Aluminiumdose
- Protection class : IP 65 Dose
- Guide tube : Edelstahl 1.4571, Ø 15 mm
- Guide Tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A ( nur mit Schirmung)
Float types
- float type 05 : Dichte: 0,81 g/cm³ | 110 mm Abstand
- float type 06 : Dichte: 0,67 g/cm³ | 135 mm Abstand
Number of contacts
- Changeover contact : 5x
- normally open : 6x
- Normally closed contact : 4x
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
QFS-55
Teflon float switch in rod design
The float switch combination is built with float switches of the QFS-50 and QFS-60 series. This makes it possible to control a level in a simple way.
Technical Data
- Material : PTFE (Teflon)
- connection cable : Silikon, Teflon
- Material rod : VA-Rohr, PTFE beschichtet
- Operating temperature : max. +150 °C
- media density : ρ ≥ 0,75 g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- Ex-protection optional : Elektrische Daten siehe EG-Prüfbescheinigung IBExU10ATEX 1089
Reed contact
- Switching current : 1 mA ... 1 A
- Switching voltage : 24 ... 250 V AC/DC
- Switching capacity : Max. 1A, 60 VA / 60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Namur circuit (1kΩ/12kQ)
- Switching current / switching voltage : nur zum Anschluss an KR-163... oder andere „Namur”-Relais
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!