CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
:
Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
Accuracy
:
+-3% vom Messbereich (30 ppm bei 3.000 ppm)
Relay output:
:
Potentialfrei
Response time
:
ca. 20 s
Operating voltage
:
24 V DC, 150 mA
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
Housing
:
Aluminium, eloxiert
Measuring element humidity
:
kapazitiv, betauungsfest
Measuring element temperature
:
Halbleiter
measuring resolution
:
12 Bit
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Option
:
Bereistellung des EDS-Files
tdata.
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Minimum air velocity across the sensor required for measurement
:
1,5 m/s
PVG-399
PVC weight with magnet insert and eyelet for cable fixing
for actuating monostable and bistable contacts
Variants
32
:
Außen Ø 25 mm x 175 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 32 u. 34 mm bis 6m Länge
37
:
Außen Ø 30 mm x 170 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 40 mm bis 6m Länge
40
:
Außen Ø 40 mm x 110 mm ca. 175g, geeignet für Rohraußen Ø 50 mm bis 6m Länge
4012
:
Außen Ø 40 mm x 110 mm ca. 300g, geeignet für Rohraußen Ø 50 mm bis 12m Länge
4016
:
Außen Ø 40 mm x 110 mm ca. 360g geeignet für Rohraußen Ø 50 mm bis 16m Länge
50
:
Außen Ø 50 mm x 130 mm ca. 255g, geeignet für Rohraußen Ø 63 mm bis 6m Länge
5012
:
Außen Ø 50 mm x 130 mm ca. 300g geeignet für Rohraußen Ø 63 mm bis 12m Länge
5016
:
Außen Ø 50 mm x 130 mm, ca. 360g, geeignet für Rohraußen Ø 63 mm bis 16m Länge
TK-315
Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99 mm
Dimensions housing type C
:
22,5 x 114,5 x 114 mm
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
4 Schließerkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
QFS-5x | QFS-6x
Teflon float switch for all kinds of liquids up to 150°C
The float of the QFS-50 and QFS-60 float switches is made of Teflon. Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Switching current / switching voltage
:
nur zum Anschluss an KR-163... oder andere „Namur”-Relais
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. +20°...–20°
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
Tank connection
:
Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
Material
:
siehe Maßbild
Material Tube
:
PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
Operating temperature
:
–20...+60 °C
Operating pressure
:
atmosphärisch
Material Float
PPH
:
Ø 70 mm 460 g
PVC
:
Ø 70 mm 455 g
PPH
:
Ø 40 mm 370g
PE
:
Ø 70 mm ca. 450 g
Material Rope
PPH
:
(rot, Ø 2 mm) ~ 2 g/m
Polyester
:
(bunt, Ø 2 mm) ~ 4 g/m
PTFE
:
(weiss, Ø 3 mm) ~ 10 g/m
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
QFS-40
Built-in float level switch
The QFS-40 built-in float switch is designed for low-cost monitoring of liquids in containers.
Technical Data
Switch housing
:
PPH| PVDF
Seal
:
NBR (PPH) | FPM (PVDF)
Operating temperature
:
PPH max. 80 °C| PVDF max. 100 °C
Operating pressure
:
max. 10 bar
Mounting position
:
horizontal (±30° von der Horizontalen)
Contact assembly
:
Schliesser-, Öffnerkontakt (je nach Einbau)
Electrical connection
:
PVC-Kabel
Switching capacity
:
max. 230 V AC/DC| max. 40 VA, max. 2 A