Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
–25...+70 °C
Wire cross-section max.
:
1,5mm²
Switching point distance between two contacts
:
min. 40 mm
Switching hysteresis
:
ca. 10-15 mm
Material
Housing
:
Polycarbonat
Mounting clip
:
V2A, Kabelbinder (PP)
Rivet
:
V2A
Screw connection
:
M 20 x 1.5, Polyamid
Weight
BK-390-50
:
137 g
BK-390-63 / BK-380
:
140 g
Switching contact
Switching voltage
:
5...250 V AC/DC
Switching current
:
1mA...6 A AC/DC
Switching capacity(min.)
:
300 VA, 60 W
Switching capacity(max.)
:
5 mW
QFS-3X
Mercury-free float switch with µ-switch
Properties
Protection class EN60529
:
IP 68
Cable entry
:
PVC , PTFE bzw. PVDF
Conductor cross-section
:
3 x 0,75 mm², PUR 3x 0,5mm²
Operating pressure cylinder
:
max. 1 bar
Operating pressure sphere
:
max. 2 bar
Switching system
:
µ-Schalter
Contact
:
Wechsler, NO, NC
Material Float
QFS-30
:
PPH (Polypropylen)
QFS-31
:
PPH (Polypropylen)
QFS-34
:
PE (Polyethylen)
Cable
TPK
:
PVC Basis Ø 5,9 mm
TPKV
:
PVC verstärkt Ø 7,3 mm
PUR
:
Polyurethan Ø 5,4 mm
SIL
:
Silikon Ø 6,4 mm
FEP
:
Teflon Ø 4,0 mm
AEM
:
Ethylen-Acrylat-Kautschuk
Cable length between float & attachment
TPK
:
70 mm
TPKV
:
90mm
PUR
:
100mm
SIL
:
80 mm
FEP
:
110 mm
AEM
:
abhängig vom Innenkabel
Operating temperature
TPK(V), AEM
:
max. + 60 °C
PUR
:
max. + 70 °C
Silicone,Tefloncable with PE float
:
max. + 80 °C
Silicone, Teflon cable with PP float
:
max. + 85 °C
MaterialDensity
QFS-31
:
≥≥ 0,6 g/cm³
QFS-34
:
≥≥ 0,75 g/cm³
QFS-30 TPK(V) cable
:
≥≥ 0,85 g/vcm³
QFS-30 PUR cable
:
≥≥ 0,95 g/cm³
QFS-30 SIL cable
:
≥≥ 0,90 g/cm³
QFS-30 FEP cable
:
≥≥ 0,95 g/cm³
QFS-30AEM cable
:
≥≥ 0,90 g/cm³
TK-301
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
05 (06)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm| 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 05
:
0,81 g/cm³
Type 06
:
0,67 g/cm³
Smart Pressostat App
App for control of ES-2X devices over Bluetooth
Android app for Bluetooth communication between smartphone or tablet and electronic safety switching devices from Fluid.iO
Properties
platform
:
Android
Android Version
:
12
T200.F-24V
Overfill protection with 24V direct connection
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
PO/ET-520
ltdata.Polyethylenanschlusskopf
:
PE/ET-521
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
max. 80 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24 V DC (24…300V DC)
Power consumption
:
≤ 1 W
Output
Output contact
:
1 potentialfreier Wechselkontakt
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 3 A AC / 3 A DC
Switching capacity
:
max. 750 VA / 90 W
Optocoupler
Switching voltage
:
max. 30 V
Switching current
:
max. 100 mA
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
Pressure range
:
0...2.000 bar gestuft
supply
:
24 V DC
Output
:
Relais 60 V AC/1A
overload
:
1,5 x Messbereich
Med. connection
:
G 1/4 Zoll
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
cIO CANopen Module
Compact I/O modules for DIN rail mounting
product series of compact CANopen I/O modules with various electrical connections
Properties
Housing
:
Kunststoffgehäuse zum Aufrasten auf DIN-Trageschienen
Dimensions
:
ca. (LxBxH) 18 x 90 x 62 mm
Internal circuits
:
Ausgangsschutzschaltungen gegen Überspannung und elektrostasche Entladung
Fieldbus and I/O level
:
getrennt durch galvanische Trennung
Process connection
:
Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
1/2/4mbar
:
2,5/5/10mbar
:
12,5/25/50mbar
:
50/100/200mbar
:
other on request
:
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class Socket
:
IP65
Float type
:
Typ 07
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10mm |15 mm | 20 mm
Accessories
:
R/I-Wandler TK-101
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
Protection class EN60529
:
IP 68
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
cable length
:
auf Wunsch
Material
Cable
:
TPK (PVC Basis)
Sensor rods
:
Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
cable material
:
FEP (Teflon) | EX (PVC blau)
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
Housing
:
Robustes Aluminiumgehäuse
Operating voltage
:
18...36V DC (max. 400 mA @18V)
Dimensions
:
150 x 119 x 82 mm (L x B x H)
Operating conditions
Operating temperature:
:
0...+70 °C (optional 0...+90 °C)
Maximum operating pressure:
:
10 bar (optional 30 bar)
Storage temperature:
:
-40...+90 °C
Connection
ModBus TCP/IP
:
Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
Digital I/O ports
:
1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
User Interface
:
grafisch über Weboberfläche im eingebundenen Netzwerk
Our application engineers advise you