Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
QFS-12
Two-Point Float-Switch
With the two-point float switch Type QFS-12 can be realized pump controls in liquid media on a simple way.
Properties
- Protection class EN60529 : IP68
- Side installation : PVC-Stopfbuchsverschraubung G 2”
- Installation from above : PVC-Stopfbuchsverschraubung G 2”
- Operating pressure : max. 2 bar
- Contact : Wechselkontakt
- Switching voltage : 4....250 V AC / DC
- Switching current : 1mA.....1A
- Switching capacity : 60W/VA
- media density : ρ ≥ 0,9 g/cm³ bis ρ ≥ 0,8 g/cm³
- Material Float : Polyethylen
Cable
- TPK : PVC Basis
- TPKV : PVC Basis verstärkt
- PUR : Polyurethan
- NEO : Neopren
- SIL : Silikon
- FEP : Teflon
- AEM : Ethylen-Acrylat-Kautschuk
Operating temperature
- TPK(V), NEO, AEM : max.+60 °C
- PUR : max.+70 °C
- FEP, SIL : max.+80 °C
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
QFS-55
Teflon float switch in rod design
The float switch combination is built with float switches of the QFS-50 and QFS-60 series. This makes it possible to control a level in a simple way.
Technical Data
- Material : PTFE (Teflon)
- connection cable : Silikon, Teflon
- Material rod : VA-Rohr, PTFE beschichtet
- Operating temperature : max. +150 °C
- media density : ρ ≥ 0,75 g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- Ex-protection optional : Elektrische Daten siehe EG-Prüfbescheinigung IBExU10ATEX 1089
Reed contact
- Switching current : 1 mA ... 1 A
- Switching voltage : 24 ... 250 V AC/DC
- Switching capacity : Max. 1A, 60 VA / 60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Namur circuit (1kΩ/12kQ)
- Switching current / switching voltage : nur zum Anschluss an KR-163... oder andere „Namur”-Relais
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
- Protection class EN60529 : IP68
- Material Float : VA 1.4571
- Material hose : Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
- Operating temperature : max. + 150 °C
- media density : ρ ≥ 0,8g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
- Operating pressure (QFS-20) : max. 15 bar
- Operating pressure (QFS-21) : max. 6 bar
LU-150
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
Lub-VDT USB-Kit
Software and USB kit for configuration & evaluation
Properties
- details : folgen
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
- connection : Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 10 (14)
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
- CE marking : siehe Konformitätserklärung
Operating temperature
- PV : max. 60°C
- PE : max 80 °C
- PP : max. 90°C
MaterialDensity
- Type 10 : 0,72 g/cm³
- Type 14 : 0,72 g/cm³
- Type 18 : 0,82 g/cm³
DTS-CAN
Flexible, digital pressure and temperature sensor with CAN bus
Media-immersed, flush-mounted, stainless steel pressure-temperature sensor with CAN bus
Properties
- Operating voltage : 9...27V
- Power consumption : 35 mA typ (50 mA max)
- Dimensions : 75x22 mm
- Process connection : G 1/4“
Measuring range
- Temperature : -20…+100 °C
- ltdata.Druck : (-1) 0…100 bar
- ltdata.AbweichungDruck : max +/- 0,5 % FS @ 0-10°C
- ltdata. :
ZS-2
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
Pressure measuring range
- 0...2,5mbar :
- 0...5mbar :
- 0...10mbar :
- 0...25mbar :
- 0...50mbar :
- 0...100mbar :
- 0...250mbar :
- 0...500mbar :
- 0...1.000mbar :
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Our application engineers advise you personally, comprehensively and professionally!