Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Ex-Polyester
Box
:
Ex-Aluminium
Properties
Protection class EN60529
:
IP 65
connection thread
:
G2"
Union nut
:
G 2¾"
Guide tube length
:
max. 6 m
Operating temperature
:
-20…+60 °C
Operating pressure
:
max. 6 bar je nach Ausführung
media density
:
ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
Ex-protection
:
siehe Baumusterprüfbescheinigung
CE marking
:
siehe Konformitätserklärung
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
Temperature:
:
-40...80°C
rel. Humidity
:
0 - 100% rH
Measuring range
measuring range (dew point)
:
-50...+80°C
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V oder 4...20mA
ZT-V
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Electrical connection
:
DIN EN 175301-803 A | DIN EN 175301-803 C | Binder M12x1 (Serie 713)
Process connection
:
G 1/4" ISO 1179-2 (Male Form E) | 1/4" NPT | 7/16" 20 UNF Male
measuring range (bar)
:
0…0,6 | 0…600
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40°C...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
ZT Serie
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
Protection class
:
IP 68
Probe body material
:
PE, PVC, PPH, PVDF
Diameter probe body
:
15 mm, 25 mm, 40 mm
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ