Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
EE-2XF
Conductive electrodes as overfill protection for Ex-Zone 0 (Cat. 1)
Conductive electrodes EE-2XF for monitoring conductive liquids within the Ex area Zone 0 (Cat. 1) for water-polluting and flammable liquids.
Properties
connection
:
Edelstahl (1.4571)
Protection class
:
IP 65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
connection thread
:
G1", G1¼", G1½”
Coating length
:
voll=ganzer Stab (10 mm am Stabende sind blank) teil =ca. 250 mm von oben
Rod diameter
:
4 oder 6 mm
rod length
:
max. 6 m
Operating pressure media side
:
max. 40 bar
Maximum permissible electrical connection values
:
Stromkreis in Zündschutzart Eigensicherheit Ex ia IIC/IIB
Connection values
:
Ui 15V | Li 10 mA | Pi 100 mW
Internal inductances / capacitances
:
vernachlässigbar klein
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Operating temperature
Category 1 Class T6...T1
:
60 °C
Category 2 Class T6
:
Medien & Umgebung 80 °C
Category 2 Class T5
:
Medien & Umgebung 95°C
Category 2 Class T4
:
Medien 130°C, Umgebung 100°C
Category 2 Class T3...T1
:
Medien 150°C, Umgebung 100 °C
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
Protection class
:
IP 68
Probe body material
:
PE, PVC, PPH, PVDF
Diameter probe body
:
15 mm, 25 mm, 40 mm
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ