Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class Socket : IP 65
- Float type : 03, 04, 09
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar (Kugel) max. 15 bar (Zylinder)
- Resolution : 7,5 mm | 10 mm
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
- Type 09 : 0,76 g/cm³
EFV2 24V
adaptive conductive electrodes with and without 24 V direct connection
The conductive electrode EFV2 is approved by the "DIBt" as an overfill prevention device for liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾", S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal, Kohlestifte
- Operating temperature : PE, PVC: atmosphärisch PPH : 90 °C, PVDF: 100 °C
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ je nach Ausführung
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Technical specifications electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24...30 V DC
- Power consumption : max. 2 W
- Switching voltage : max. 230 V AC / V DC min. 5 V DC (CMOS-Relais)
- Switching current : max. 0,12 A AC / A DC min. <1 mA
- Switching capacity : max. 25 VA / W
- Sensitivity : 3k … 100 kΩ
T204.F
with general building authority approval Z-65.11-404
Properties
- connection : Polyester Dose | Aluminium Dose
- Protection class : IP 65 Dose
- number of floats : max. 4x
- Operating temperature : max. 135 °C
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : max. 3x Wechsler | 5x Schließer | 3x Öffner
- Switching current : 1 A, 2 A (nur mit Schirmung)
- Switching voltage : 230 V AC
Float
- Stainless steel ball 52mm Ø : max. 20 bar | 0,75 g/cm³
- Stainless steel ball 61 mm Ø : max. 20 bar | 0,65 g/cm³
- Stainless steel cylinder 44 mm Ø : max. 15 bar | 0,76 g/cm³
- min. contact gap type 03 : 75 mm
- min. contact gap type 04 : 85 mm
- min. contact gap type 09 : 75 mm
Switching contacts and switching capacity
- Changeover contact : max. 3x | 60W/VA
- normally open : max. 5x | 100 W / VA
- Normally closed contact : max. 3x | 60 W/VA
T-20X
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
- Housing : Kunststoff
- Power supply 24V : 24V DC | 230V
Measuring element and parameter
- Measuring principle : optisch, NDIR
- measuring grid : 2 sec.
- Accuracy : ± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
Operating conditions
- Operating temperature : 0…+50 °C
- Storage temperature : -30 °C…+75 °C
- Operating humidity : 0…85% rH (nicht kondensierend)
- Storage humidity : 0…85% rH (nicht kondensierend)