HD-100 | HD-102 | HD-104
Hydrostatic immersion probes (0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP68
- Operating temperature : -10...70 °C (PVC: -10...60 °C)
- Storage temperature : -25...70 °C (PVC: -10...60 °C)
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : abhängig vom Messbereich
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik Al2o3 96%, Keramik Al2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- Cable : PVC, PUR, FEP (Ø8 mm; 2 x 0,25 mm2 mit Luftschlauch und PTFE-Filter
ZMF-202e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0...17.000ppm : 0…1,7 vol% (100 % LEL)
- 0...21.000ppm : 0…2,1 vol%
Options
- Other cable lengths on request :
- ATEX certification (optional) :
TK-308
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 11,12, 15, 17
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
Operating temperature
- PVC : max. 60 °C
- PE : max. 80 °C
- PP : max. 90 °C
MaterialDensity
- Type 11 : 0,60 g/cm³
- Type 12 : 1,00 g/cm³
- Type 15 : 0,59 g/cm³
- Type 17 : 0,63 g/cm³
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- ltdata.MessbereichNenndruck : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- ltdata.Medientemperatur(optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- ltdata.Standard : Binder M12 x 1
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
- measuring range (Humidity) : 0…100 % rF,
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- Signal output : I2C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000…1.500 ppm
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
- measuring range (Humidity) : 0...100 % rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80 °C
- Measuring accuracy (temperature) : ± 0,2 °C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000...1.500 ppm
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Box : Polyethylen-Anschlusskopf (PE)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
EF2 24...230 V
Conductive electrodes with 24...230 V direct connection
The EF2 overfill protection (24...230 V AC/DC) is approved by "DIBt" as an overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G1"
- Union nut : auf Wunsch
Material
- Screw connection : PE, PVC, PPH, PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Sensitivity range : einstellbar 2…100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PTFE : 100 °C
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : < 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC /30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED Grün, Funktions-LED Rot
- Switching delay : ca. 0,5 s Anzug / Abfall
- CE marking : siehe Konformitätserklärung
Our application engineers advise you personally, comprehensively and professionally!