The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W
The water level gauge is particulary suitable for all liquid media which are aggressively hot and rapidly moved in a container, but are not too much contamined.
Properties
Tank connection
:
Flansch ab DN 25 oder Verschraubung ab G ½"
Material Float
:
PPH max. 2,5 bar, Glas max. 10 bar
cable length
:
bei monostabilem Kontakt: Standard 2 m
Number of contacts
:
beliebig
Contact distance
:
min. 10 mm
Temperature of the fluid
:
mit Plexiglasrohr max. +70 °C
media density
:
ρ ≥ 0,95 g/cm³ | ρ ≥ 0,85 g/cm³ (auf Wunsch)
Properties W-350
Material tube sight glass
:
transparentes PVC
Temperature of the fluid
:
max. +60 °C
Operating pressure
:
max. 2,5 bar
Material flange
:
PVC
Material connection with angle valve
:
PVC
Material sealing ring
:
Gummi
Properties W-351
Material tube sight glass
:
Hartglas, Plexiglas
Temperature of the fluid
:
max. +120 °C
Material flange
:
Rotguss
Material connection with angle valve
:
Rotguss
Material sealing ring
:
Silikon
Operating pressure with glass tube
:
max. 10 bar
Operating pressure with plexiglass tube
:
max. 2 bar
Properties W-352
Material tube sight glass
:
Hartglas, Plexiglas
Temperature of the fluid
:
max. +120 °C
Material flange
:
Edelstahl
Material connection with angle valve
:
Edelstahl 1.4571 als Bogen 90°
Material sealing ring
:
PTFE und Viton
Operating pressure with glass tube
:
max. 10 bar
Operating pressure with plexiglass tube
:
max. 2 bar
Properties W-353
Material tube sight glass
:
Hartglas, Plexiglas
Temperature of the fluid
:
max. +120 °C
Material flange
:
Edelstahl
Material connection with angle valve
:
Edelstahl 1.4401
Material sealing ring
:
PTFE und Viton
Operating pressure with glass tube
:
max. 10 bar
Operating pressure with plexiglass tube
:
max. 2 bar
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties KS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
2 Wechselkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ltdata.
:
BI
Bistable Switch
Properties
Protection class
:
IP 65
Switching current
:
max. 1 A
Switching voltage
:
max. 24 V
Switching capacity
:
max. 20 W/VA
Material
Housing
:
Messingrohr Ø 10 x 1
Cable
:
TPK (PVC basis) | SIL (Silikon)
Operating temperature
TPK
:
–15 ° ... + 60 °C
SIL
:
–15 ° ... +130 °C
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
PVS-390
PVC float with magnet insert
for actuating monostable and bistable contacts
Variants
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
connection thread
:
G 1/2” Standard | G 3/4” | G1”
Cable
:
TPK (Standard) | SIL (Silikon) | FEP (Teflon)
rod length
:
max. 6.000 mm
Operating pressure
:
max. 40 bar
Material
electrode body
:
Edelstahl 1.4571
Process connection
:
Edelstahl 1.4571
Coating
:
PTFE
electrode rod
:
Edelstahl 1.4571
on request
:
Hastelloy C | Tantal
Our application engineers advise you
personally, comprehensively and professionally!