CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
:
Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
Accuracy
:
+-3% vom Messbereich (30 ppm bei 3.000 ppm)
Relay output:
:
Potentialfrei
Response time
:
ca. 20 s
Operating voltage
:
24 V DC, 150 mA
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
Dimensions
:
180 x 48 x 36,5 mm ( L x B x H )
Weight
:
ca. 1,5 kg
Protection class
:
IP68
Cable length (standard)
:
15 m
Bending radius
:
> 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
Temperature range
:
0°C ... 50°C
Mounting shoe material
:
V2A 1,5mm
Certificates
EX / ATEX
:
IBExU 04 ATEX 1256
Measuring principle
Flow velocity: Ultrasonic Doppler
:
Filling level: Differential pressure
:
Flow velocity
Measuring range
:
0,01 - 4 m / s
Measuring accuracy
:
+/- 5 % vom Momentanwert im Kanal
Temperature drift
:
0,1% / °C ( Meßspanne )
Temperature drift
:
0,05% / °C ( Nullpunkt )
Output signal
:
4 - 20 mA
Filling level
Measuring ranges
:
0 –1 m ; 0 – 2 m ; 0 – 4 m
Measuring accuracy
:
< 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
Temperature drift
:
0,005% / °C v.E. Meßspanne
Temperature drift
:
0,005% / °C v.E. Nullpunkt
Material
:
Al2O3 (96%) aktive Fläche
Output signal
:
4 – 20 mA
Zero point
:
norm 4 mA ( +/- 3 % )
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties KS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
ZMF-203e-IR
Robust sulphur hexafluoride sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-203e-IR is an SF6 sensor for measuring sulphur hexafluoride concentration in harsh environments.
Properties
Operating conditions
:
-40 °C…+60 °C
Storage conditions
:
-40 °C…+85 °C
RelativeHumidity
:
0…95 % nicht kondensierend
Measurement method
:
NDIR (dual beam technology)
Certification
:
SIL2, ATEX
Signal output
:
4..20mA
Power supply
:
12…24 V DC
Housing
:
Edelstahl
Standard cable length
:
1,5 m
pressure conditions
:
800...1200 mbar
screw thread
:
M46x15
Measuring ranges
in ppm
:
in vol%
0...1.000ppm
:
0...0,1 vol%
0...2.000ppm
:
0...0,2 vol%
Options
Other cable lengths on request
:
ATEX certification (optional)
:
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Box
:
Polyethylen-Anschlusskopf (PE)
Cable
:
Kabel (TPK)
Plug
:
Stecker (ST)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Our application engineers advise you
personally, comprehensively and professionally!