Aero_aH100
Exhaust air fan with integrated dehumidification control for automatic room dehumidification
Dehumidification control, including integrated indoor and outdoor climate sensor. Controlled dehumidification takes place by comparing the indoor and outdoor climate. To support room dehumidification, a ventilation fan can be directly connected and controlled via the Aero_aH 100.
Properties
- Power supply : 230V~ 50Hz
- power consumption : 8 W
- Protection class : IPX4
- flow rate : 78 m³/h bis zu 92 m³/h
- color : verkehrsweiß, ähnlich RAL 9016
- Material : Kunststoff
- Noise level : 27 dB(A) / 32 dB(A)
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100% rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
KST-20 Vento-RN
Climate control with aH-Controlled technology and Rn-Protected seal
The KST-20 Vento/RN is a climate control unit with aH-Controlled technology and Rn-Protected seal for ventilation and dehumidification of all types of private, commercial and industrial rooms. With the three operating modes for ventilation, dehumidification and radon measurement, the KST-20 Vento climate control unit can be used flexibly in almost all living, working and industrial areas.
Properties
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertigem ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100 % rF
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- measuring range (radon) : 0...1200 Bq/m³
- Adjustable limits : 80...1000 Bq/m³
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
T201 PTFE
Immersible Magnetic Probe made of PTFE
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
ZMF-202e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0...17.000ppm : 0…1,7 vol% (100 % LEL)
- 0...21.000ppm : 0…2,1 vol%
Options
- Other cable lengths on request :
- ATEX certification (optional) :
T209
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
MO
Monostable Switch
Properties
- Protection class : IP 65
- Switching current : max. 1 A
- Switching voltage : max. 24 V
- Switching capacity : max. 20 W/VA
Material
- Housing : Messingrohr Ø 10 x 1
- Cable : TPK (PVC basis) | SIL (Silikon)
Operating temperature
- TKP : –15 ° ... + 60 °C
- SIL : –15 ° ... +130 °C
T-200.L 24V
Leakage probes with general building authority approval
The leakage probes T-200.L (24 V) are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Head : Polyethylenanschlusskopf (PE)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24 V DC (24...30 V DC)
- Power consumption : ≤ 1 W
Output
- Output contact : 1 potentialfreier Wechselkontakt
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 3 A AC / 3 A DC
- Switching capacity : max. 750 VA / 90 W
Optocoupler
- Switching voltage : max. 30 V
- Switching current : max. 100 mA
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
cIO CANopen Module
Compact I/O modules for DIN rail mounting
product series of compact CANopen I/O modules with various electrical connections
Properties
- Housing : Kunststoffgehäuse zum Aufrasten auf DIN-Trageschienen
- Dimensions : ca. (LxBxH) 18 x 90 x 62 mm
- Internal circuits : Ausgangsschutzschaltungen gegen Überspannung und elektrostasche Entladung
- Fieldbus and I/O level : getrennt durch galvanische Trennung
ElectricalConnection
- Operating voltage : 11...32V DC (typ. 24V DC)
- Operating temperature : 0...+55 °C
- Operating temperature : optional -40...+70 °C
- Conductor cross-section : 0,08...1,5 mm² (AWG28...AWG14)
CAN bus properties
- baud rate (max.) : 1 MBit
- ciA Standards : Ds301 Version 4.2 & DS401 Version 3.0
- ISO standards : ISO11898 (+ Transceiver TJA1050)
- PDO : siehe Dokumente
QFS-12
Two-Point Float-Switch
With the two-point float switch Type QFS-12 can be realized pump controls in liquid media on a simple way.
Properties
- Protection class EN60529 : IP68
- Side installation : PVC-Stopfbuchsverschraubung G 2”
- Installation from above : PVC-Stopfbuchsverschraubung G 2”
- Operating pressure : max. 2 bar
- Contact : Wechselkontakt
- Switching voltage : 4....250 V AC / DC
- Switching current : 1mA.....1A
- Switching capacity : 60W/VA
- media density : ρ ≥ 0,9 g/cm³ bis ρ ≥ 0,8 g/cm³
- Material Float : Polyethylen
Cable
- TPK : PVC Basis
- TPKV : PVC Basis verstärkt
- PUR : Polyurethan
- NEO : Neopren
- SIL : Silikon
- FEP : Teflon
- AEM : Ethylen-Acrylat-Kautschuk
Operating temperature
- TPK(V), NEO, AEM : max.+60 °C
- PUR : max.+70 °C
- FEP, SIL : max.+80 °C
Our application engineers advise you personally, comprehensively and professionally!