Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99 mm
Dimensions housing type C
:
22,5 x 114,5 x 114 mm
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
4 Schließerkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
Pressure range
:
0...500mbar gestuft
supply
:
12 - 24 V DC
Output
:
Relais 230 V/1A
overload
:
2 x Messbereich
Med. connection
:
Schlauch
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
LGW-13
CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
:
Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Ex-Polyester
Box
:
Ex-Aluminium
Properties
Protection class EN60529
:
IP 65
connection thread
:
G2"
Union nut
:
G 2¾"
Guide tube length
:
max. 6 m
Operating temperature
:
-20…+60 °C
Operating pressure
:
max. 6 bar je nach Ausführung
media density
:
ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
Ex-protection
:
siehe Baumusterprüfbescheinigung
CE marking
:
siehe Konformitätserklärung
T20x.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
TK-30X
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
connection thread
:
G 3/8”, G 1/2”, G 1”, G 1 1/2”, G 2”, G 3”
connection cable
:
LiYY max. 80 °C | Silikon max. 130 °C
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. +60...+130 °C | min. –20...–10 °C je nach Ausführung
Operating pressure
:
max. 20 bar je nach Ausführung
media density
:
siehe Schwimmerdaten
Viscosity
:
< 100 cp
Switching hysteresis
:
ca. halbe Auflösung
Resolution
:
7,5 mm, 10 mm, 15 mm, 20 mm oder 1 %, 2 %, 5 % je nach Ausführung
Total resistance
:
ca. 5 kΩ
Measuring voltage
:
max. 24 V
Measuring current
:
max. 5 mA
Our application engineers advise you