Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
details
:
folgen
T200.F-24V
Overfill protection with 24V direct connection
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
PO/ET-520
ltdata.Polyethylenanschlusskopf
:
PE/ET-521
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
max. 80 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24 V DC (24…300V DC)
Power consumption
:
≤ 1 W
Output
Output contact
:
1 potentialfreier Wechselkontakt
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 3 A AC / 3 A DC
Switching capacity
:
max. 750 VA / 90 W
Optocoupler
Switching voltage
:
max. 30 V
Switching current
:
max. 100 mA
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
Housing
:
Kunststoff
Power supply 24V
:
24V DC | 230V
Measuring element and parameter
Measuring principle
:
optisch, NDIR
measuring grid
:
2 sec.
Accuracy
:
± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
Android app for Bluetooth communication between smartphone or tablet and electronic safety switching devices from Fluid.iO
Properties
platform
:
Android
Android Version
:
12
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
ViscoScope® VA-100
Inline Viscometer
Maintenance-free inline viscosity sensor for precise and reliable real-time measurement of viscosity directly in the process.
Properties
Material
:
1.4571 / 1.4404 (316Ti / 316L)
Protection class
:
IP65
Process temperature
:
-10°C … +130°C | (integriertes Pt100 im Messfühler)
max. process pressure
:
Vakuum ... 64 bar
Process connections
:
NPT | M48 | Varivent® | Tri-Clamp
Cable length sensor - transmitter
:
Max. 1.000 Meter
max. flow velocity
:
5 m / sec
Ex approval
:
II 1/2G Ex ia IIC T6...T3 Ga/Gb | (optional)
Sensor types
Sphere
:
VA-100B
Cylinder
:
VA-100C
Repeatability
VA-100B
:
± 0,5% | ± 1 Digit
VA-100C
:
± 0,3% | ±1 Digit
Measuring ranges
VA-100B
:
0,1 - 2.500 mPa·s x g/cm³
VA-100C
:
10 - 25.000 mPa·s x g/cm³
Probe dimensions
VA-100B
:
Ø 32 x 145 mm
VA-100C
:
Ø 32 x 120 mm
installation positions
Reservoir
:
tanks
:
Pipe
:
flow cell
:
Installation is position-independent
:
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties TPS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…100% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-50...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties KS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
10 (14)
connection cable
:
1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating pressure
:
max. 6 bar
Resolution
:
10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
CE marking
:
siehe Konformitätserklärung
Operating temperature
PV
:
max. 60°C
PE
:
max 80 °C
PP
:
max. 90°C
MaterialDensity
Type 10
:
0,72 g/cm³
Type 14
:
0,72 g/cm³
Type 18
:
0,82 g/cm³
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
Our application engineers advise you