Cart
product added to request
MKL configure
TK-302 configure
ZT-S configure
Ex-BK configure
Fluidix Lub-VDT configure
TK-307-0 configure
TK-309 configure
TK-309-0 configure
NP-255 configure
XR-4x0 | XR-4x1 configure
XR-4x2 configure
GSB-390 configure
T200.F-24V configure
MKL
Magnetic Flap Indicator
The MKL level indicator is connected by its two connections to the container to be monitored (see connection example). According to the law of interconnected containers the level in the float chamber corresponds exactly to the level in the container
Properties
- connection : Flansch ab DN 15
- Material : rostfreier Edelstahl, PVC, PPH, PVDF
- Material flange : Edelstahl 1.4571, C22.8
- Material Float : Edelstahl, Titan, PVC, PPH, PVDF
- Number of contacts : beliebig
- Contact load : max 10 VA, max 230 V AC
- Display length : max. 6m
Operating temperature
- PTFE seal : max. 150 °C
- Stainless steel: Klingerit seal : max. 200 °C
- PVC : max. 60 °C
- PPH : max. 90 °C
- PVDF : max. 130 °C
Stainless steel float
- Weight : ~ 300 g
- Dimensions : Ø 52 x 270
- Operating pressure : 16 bar
- media density : ρ ≥ 0,70 g/cm³
Stainless steel float
- Weight : ~ 320 g
- Dimensions : Ø 52 x 270
- Operating pressure : 40 bar
- media density : ρ ≥ 0,75 g/cm³
Titanium float
- Weight : ~ 180 g
- Dimensions : Ø 52 x 150
- Operating pressure : 16 / 40 bar
- media density : ρ ≥ 0,73 g/cm³
PVC float
- Weight : ~ 331 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,8 g/cm³
PPH float
- Weight : ~ 283 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,69 g/cm³
PVDF float
- Weight : ~ 352 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,85 g/cm³
TK-302
Level transducer made of brass and stainless steel
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 03 (04)
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- Resolution : 10 mm | 15 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
- Housing : Robustes Aluminiumgehäuse
- Operating voltage : 18...36V DC (max. 400 mA @18V)
- Dimensions : 150 x 119 x 82 mm (L x B x H)
Operating conditions
- Operating temperature: : 0...+70 °C (optional 0...+90 °C)
- Maximum operating pressure: : 10 bar (optional 30 bar)
- Storage temperature: : -40...+90 °C
Connection
- ModBus TCP/IP : Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
- Digital I/O ports : 1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
- User Interface : grafisch über Weboberfläche im eingebundenen Netzwerk
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- Measuring range nominal pressure : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- fluid temperature (optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- Standard : Binder M12 x 1
Ex-BK
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –20...+120 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
- Dimensions : 80 mm x 75 mm x 57 mm
Material
- Housing : Aluminium
- Mounting clip : V2A
- Rivet : V2A
- Screw connection : M 20 x 1.5, V2A
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 24...250 V AC/DC
- Switching current : 20 mA...6 A AC/DC
- Switching capacity(min.) : max. 500 VA, 60 W
- Switching capacity(max.) : min. 2 VA/W
Fluidix Lub-VDT
Oil condition sensor for permanent monitoring of mechanical properties of liquids
The FluidIX Lub-VDT enables inline monitoring of mechanical fluid properties.
Properties
- CE marking : EN 61000-6-1/2/3/4
- Operating voltage : 9...32 V DC
- Housing material : Edelstahl
- Protection class : IP 67
- Dimensions : 30x90 mm
- Process connection : G 3/8"
- Electrical connection : M12-8 A-Coding
- Weight : 150g
- Measurement output : 2x 4...20mA
- bus protocol : ModbusRTU, CANopen
Measured variables
- Resonator frequency : 20...25 kHz
- Viscosity : 1-650 cSt (mm²/s)
- density : 0.5-1.5 g/cm³
- Temperature : -40...+125°C
- sampling rate : 1/s
Operating conditions
- Temperature of the fluid : -40...+125°C
- Housing temperature : -40...+100°C
- oil pressure : Max. 50 bar
- particle size : 250 μm
T204
Magnetic immersion probe made of stainless steel (1.4571)
For use with highly aggressive liquid media to detect level limit values in containers. Suitable for use in hazardous areas, zone 0 (category 1).
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- connection thread : G1 1/2" | G2"
- Sliding tube length : max. 6000 mm (Rohr Ø 12 mm)
- Operating pressure : max. 20 bar (Kugel) | max. 15 bar (Zylinder)
- Operating temperature : max. 135 °C
- Number of floats : max. 4
Float type
- Stainless steel ball 52mm ⌀ : Dichte: 0,75 g/cm³ | mind. Kontaktabstand: 75 mm
- Stainless steel ball 62mm ⌀ : Dichte: 0,65 g/cm³ | mind. Kontaktabstand: 85 mm
- Stainless steel cylinder 44 mm Ø : Dichte: 0,76 g/cm³ | mind. Kontaktabstand: 75 mm
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 4
- normally open : 6
- Normally closed contact : 4
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
- Housing : Kunststoff
- Protection class : IP00
- Ambient temperature : -20…+60°C
- Supply voltage : 24V DC +20% / -10%
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
- Connection aluminium box : H30 x B50 x T45 mm
- Connection polyester box : H56 x B80 x T75 mm
- connection cable : 1000 mm PUR blau
- Protection class Socket : IP65
- Material Sliding tube : VA 1.4571
- Material of the angle fastening : VA 1.4408
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 07
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- media density : Typ 07: 0,54 g/cm³
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
- Accessories : R/I-Wandler TK-101
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class Socket : IP65
- Float type : Typ 07
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : Typ 07: 0,54 g/cm³
- Resolution : 7,5 mm | 10mm |15 mm | 20 mm
- Accessories : R/I-Wandler TK-101
NP-255
Level Switch - multiple 2...4 - pneumatic
very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
- Protection class EN60529 : IP 54
- connection thread : ab G2”
- Union nut : ab G2¾”
- Container connection flange : ab DN 25
- Hose Ø : 16 mm
- Operating temperature : +60 °C
- medium temperatur : max. +60 °C
- Contact : Wechsler
- Switching capacity : 500 VA
- Switch-on point (Viton membrane) : 150 mm WS ±30 mm
- Switch-off point (MembraneViton) : 90 mm WS ±30 mm
Material
- Pitot tube / Hose : PVC
- Screw fitting/grommet : PVC
- flange : PVC
- Connection head : PVC
Switching voltage
- silver : max. 250 V AC
- Gold : max. 24 V AC
Switching current
- silver : max. 6 A
- Gold : max. 100 mA
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
XR-4x2
Electrode relay with ATEX and WHG approval
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
GSB-390
Glass float with magnet insert
for actuating monostable and bistable contacts
Variants
- 150 : AußenØ 26,5 x 150 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 50 g
- 190 : AußenØ 26,5 x 190 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 61 g
- 205 : AußenØ 26,5 x 205 mm (3 Magnete auch für bistabile Kontakte) Gewicht ca. 69 g
T200.F-24V
Overfill protection with 24V direct connection
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Polyester junction box : PO/ET-520
- Polyethylene connection head : PE/ET-521
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24 V DC (24…300V DC)
- Power consumption : ≤ 1 W
Output
- Output contact : 1 potentialfreier Wechselkontakt
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 3 A AC / 3 A DC
- Switching capacity : max. 750 VA / 90 W
Optocoupler
- Switching voltage : max. 30 V
- Switching current : max. 100 mA
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!