The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
Protection class EN60529
:
IP68
Material Float
:
VA 1.4571
Material hose
:
Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
Operating temperature
:
max. + 150 °C
media density
:
ρ ≥ 0,8g/cm³
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Operating pressure (QFS-20)
:
max. 15 bar
Operating pressure (QFS-21)
:
max. 6 bar
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
Tank connection
:
Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
Material
:
siehe Maßbild
Material Tube
:
PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
Operating temperature
:
–20...+60 °C
Operating pressure
:
atmosphärisch
Material Float
PPH
:
Ø 70 mm 460 g
PVC
:
Ø 70 mm 455 g
PPH
:
Ø 40 mm 370g
PE
:
Ø 70 mm ca. 450 g
Material Rope
PPH
:
(rot, Ø 2 mm) ~ 2 g/m
Polyester
:
(bunt, Ø 2 mm) ~ 4 g/m
PTFE
:
(weiss, Ø 3 mm) ~ 10 g/m
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
Temperature:
:
-40...80°C
rel. Humidity
:
0 - 100% rH
Measuring range
measuring range (dew point)
:
-50...+80°C
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V oder 4...20mA
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
ltdata.Polyesterdose
:
ltdata.Aluminiumdose
:
ltdata.Polyethylenanschlusskopf
:
Cable
:
Plug
:
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Operating temperature
:
atmosphärisch
ltdata.BetriebstemperaturPP
:
max. 90°C
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
07
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Accessories
:
R/I-Wandler TK-101
Smart Pressostat App
App for control of ES-2X devices over Bluetooth
Android app for Bluetooth communication between smartphone or tablet and electronic safety switching devices from Fluid.iO
Properties
platform
:
Android
Android Version
:
12
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
connection thread
:
G 3/8”, G 1/2”, G 1”, G 1 1/2”, G 2”, G 3”
connection cable
:
LiYY max. 80 °C | Silikon max. 130 °C
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. +60...+130 °C | min. –20...–10 °C je nach Ausführung
Operating pressure
:
max. 20 bar je nach Ausführung
media density
:
siehe Schwimmerdaten
Viscosity
:
< 100 cp
Switching hysteresis
:
ca. halbe Auflösung
Resolution
:
7,5 mm, 10 mm, 15 mm, 20 mm oder 1 %, 2 %, 5 % je nach Ausführung
Total resistance
:
ca. 5 kΩ
Measuring voltage
:
max. 24 V
Measuring current
:
max. 5 mA
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
TK-320
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-321
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-322
:
19” Karteneinschub 7 TE, 3 HE
Properties
Protection class EN60529
:
IP 52
Operating temperature
:
– 20 °C...+60 °C
nominal voltage
:
24 V DC...230 V AC
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | Bürde max. 500 Ω
Relay
:
2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
Number of LEDs
:
33 (rot/grün); 32 (TK-322)
Resolution
:
ca. 3,5 %
Error
:
± 1 LED
connection
:
Schraubklemmen
connection TK-322
:
Steckerleiste
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | max. load 500 Ω
Relay(2xSwitch)
:
max. 230 V | min. 5 V
Relay(2xSwitch)
:
max. 3 A | min. 1 mA
VS-D250
Transmitter for ViscoScope viscosity sensors
Maximum flexibility for an optimal choice of measuring instrument: The VS-D250 transmitter is compatible with all ViscoScope® sensors of the types VA-100 and VA-300.
Properties
Output card socket
:
2
External input
:
0/4…20 mA | 0/2…10 V DC
Power supply
:
24V DC, 12 W
Dimensions
:
142 x 106 x 73 mm (L x B x H)
Front
:
RS232, MODBUS RTU (Standard)
Display and Operation
Lines
:
4
Pages
:
2
Character set
:
alphanumerisch
Buttons
:
3 (front)
Alarms
system function
:
sensor diagnosis
:
Coil Temperature
:
2 configurable LEDs
:
optional outputs
0/4…20mA | 0/2…10V DC (active)
:
RS232 | RS485
:
2 SPDT-Relays: RS232 | RS485
:
Filter
Moving average (200 measured values)
:
Our application engineers advise you
personally, comprehensively and professionally!