very reliable and simple
sensors for scanning liquids, in
particular when used for overflow
protection. liquids can be
aggressive, sticky or highly contaminated
Properties
Protection class EN60529
:
IP 54
connection thread
:
ab G2”
Union nut
:
ab G2¾”
Container connection flange
:
ab DN 25
HoseØ
:
13x2 mm
Operating temperature
:
+60 °C
medium temperatur
:
max. +60 °C
Contact
:
Wechsler
Switching capacity
:
500 VA
Switch-on point (Viton membrane)
:
150 mm WS ±30 mm
Switch-off point (MembraneViton)
:
90 mm WS ±30 mm
Material
Hose
:
PVC
Screw fitting/grommet
:
PVC
flange
:
PVC
Connection head
:
PVC
Switching voltage
silver
:
max. 250 V AC
Gold
:
max. 24 V AC
Switching current
silver
:
max. 6 A
Gold
:
max. 100 mA
EK-CAN
PC program for CANopen sensors
Evaluation and configuration software for Fluid.iO CANopen sensors
Properties
Operating system
:
Windows
ltdata.BuildVersion
:
1.0.5 (28.10.2025)
installation type
:
ZIP, portable
ltdata.Sprache
:
DE | EN
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
Housing
:
Robustes Aluminiumgehäuse
Operating voltage
:
18...36V DC (max. 400 mA @18V)
Dimensions
:
150 x 119 x 82 mm (L x B x H)
Operating conditions
Operating temperature:
:
0...+70 °C (optional 0...+90 °C)
Maximum operating pressure:
:
10 bar (optional 30 bar)
Storage temperature:
:
-40...+90 °C
Connection
ModBus TCP/IP
:
Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
Digital I/O ports
:
1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
User Interface
:
grafisch über Weboberfläche im eingebundenen Netzwerk
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
Temperature:
:
-40...80°C
rel. Humidity
:
0 - 100% rH
Measuring range
measuring range (dew point)
:
-50...+80°C
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V oder 4...20mA
cIO CANopen Module
Compact I/O modules for DIN rail mounting
product series of compact CANopen I/O modules with various electrical connections
Properties
Housing
:
Kunststoffgehäuse*
Dimensions (LxBxH)
:
18 x 90 x 62 mm
Internal circuits
:
Ausgangsschutzschaltungen gegen Überspannung und elektrostasche Entladung
Fieldbus and I/O level
:
getrennt durch galvanische Trennung
ciA Standards
:
Ds301 Version 4.2 & DS401 Version 3.0
ISO standards
:
ISO11898 (+ Transceiver TJA1050)
PDO
:
siehe Dokumente
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
Process connection
:
Schlauchanschluss 4 mm oder 6 mm
Cable gland
:
PG 7
TK-301
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
05 (06)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm| 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 05
:
0,81 g/cm³
Type 06
:
0,67 g/cm³
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
Housing
:
Aluminium
Protection class
:
IP30
Dimensions
:
197 x 153 x 37,5mm (B x H x T)
Temperature range
:
0 – 50°C
Supply voltage
:
24V DC +/-20%
Power consumption
:
120mA – 220mA
Reverse polarity protection
:
✓
Display
:
4x20
Outputs
analog 0(4)–20mA
:
3x
digital
:
4x
fixed for alarm
:
1x
free configurable
:
3x
display of measured value
Flow velocity
:
Filling level
:
flow
:
flow rate
:
Our application engineers advise you