Cart
product added to request
LU-1X0 configure
HD-110 | HD-112 | HD-114 configure
ViscoScope® VA-300 configure
MO configure
TK-101 configure
ES-Serie configure
TK-309-0 configure
TK-309 configure
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
ViscoScope® VA-300
Maintenance-free inline process viscometer for real-time viscosity measurement
The ViscoScope® sensors are made of high-quality, first-class stainless steel and impress with their intelligent, robust design.
Properties
- Protection class : IP65
- Material : 1.4571 / 1.4404 (316Ti / 316L)
- Process temperature : -40°C … +450°C
- Process pressure : Vakuum ... 450 bar
- Process connections : DIN Flansch | ANSI Flansch | NPT | Varivent® | Tri-Clamp
- Cable length sensor - transmitter : max. 1.000m
- max. flow velocity : 10 m / sec
- Ex approval : (optional) II 1/2G Ex ia IIC T6...T3 Ga/Gb
- Material (optional) : Hastelloy C22, Duplex 2205, Teflon
Sensor types
- big cylinder : VA-300L
- small cylinder : VA-300M
- Sphere : VA-300H
- small sphere : VA-300X
Measuring range
- VA-300L : 0,1 - 2.500 mPa·s x g/cm³
- VA-300M : 1 - 25.000 mPa·s x g/cm³
- VA-300H : 0,01...250 Pa·s x g/cm³
- VA-300X : 0,1...2.500 Pa·s x g/cm³
Probe dimensions
- VA-300L : Ø 32 x 190 mm
- VA-300M : Ø 32 x 165 mm
- VA-300H : Ø 32 x 130 mm
- VA-300X : Ø 19 x 115 mm
MO
Monostable Switch
Properties
- Protection class : IP 65
- Switching current : max. 1 A
- Switching voltage : max. 24 V
- Switching capacity : max. 20 W/VA
Material
- Housing : Messingrohr Ø 10 x 1
- Cable : TPK (PVC basis) | SIL (Silikon)
Operating temperature
- TKP : –15 ° ... + 60 °C
- SIL : –15 ° ... +130 °C
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
- Housing : Kunststoff
- Protection class : IP00
- Ambient temperature : -20…+60°C
- Supply voltage : 24V DC +20% / -10%
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
- Housing : Robustes Aluminiumgehäuse
- Operating voltage : 18...36V DC (max. 400 mA @18V)
- Dimensions : 150 x 119 x 82 mm (L x B x H)
Operating conditions
- Operating temperature: : 0...+70 °C (optional 0...+90 °C)
- Maximum operating pressure: : 10 bar (optional 30 bar)
- Storage temperature: : -40...+90 °C
Connection
- ModBus TCP/IP : Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
- Digital I/O ports : 1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
- User Interface : grafisch über Weboberfläche im eingebundenen Netzwerk
TK-101
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
T208
Immersible Magnetic Probe made of PVC, PE, PPH
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
ES-Serie
electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class Socket : IP65
- Float type : Typ 07
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : Typ 07: 0,54 g/cm³
- Resolution : 7,5 mm | 10mm |15 mm | 20 mm
- Accessories : R/I-Wandler TK-101
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
T207
Magnetic immersion probes made of PPH
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- details : folgen
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
- Pressure range : 0...2.000 bar gestuft
- supply : 24 V DC
- Output : Relais 60 V AC/1A
- overload : 1,5 x Messbereich
- Med. connection : G 1/4 Zoll
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 07
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- media density : Typ 07: 0,54 g/cm³
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
- Accessories : R/I-Wandler TK-101
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!