Cart
product added to request
ÜTA-32 configure
QFS-2X configure
EP 24V configure
QFS-55 configure
T20x.F configure
BK-390 configure
ZMF-100-IR configure
ZMF-200e-IR configure
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
- measuring range (Humidity) : 0…100 % rF,
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- Signal output : I2C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000…1.500 ppm
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
- measuring range (Humidity) : 0...100 % rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80 °C
- Measuring accuracy (temperature) : ± 0,2 °C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000...1.500 ppm
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
- connection : G 1” (andere Gewinde auf Anfrage)
- max.length guide tube : siehe Diagramm
- Operating temperature : atmosphär. Bedingungen
- Operating pressure : atmosphär. Bedingungen
- media density : siehe Eintauchtiefe
- Number of contacts : beliebig
- Contact load : max. 10 VA, max. 230 V AC
- Length : max. 1750 mm
Material
- Sight tube : PVC transparent
- connection : PVC-Verschraubung mit PTFE-Stangenführung
- Guide rod : Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
- float : PE / PP
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
- Protection class EN60529 : IP68
- Material Float : VA 1.4571
- Material hose : Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
- Operating temperature : max. + 150 °C
- media density : ρ ≥ 0,8g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
- Operating pressure (QFS-20) : max. 15 bar
- Operating pressure (QFS-21) : max. 6 bar
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
T205 VA
Stainless steel magnetic immersion probes
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : max. 2x Typ 08
- connection cable : Silikon Litze
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar (Zylinder)
- Number of contacts : max. 2 x Schließer/ Öffner wahlweise durch 180°-Drehung des Schwimmers bei 2 Schwimmern
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
- Sliding tube length : max. 1000 mm
- media density : Typ 08: 0,78 g/cm³
- float : Zylinder Edelstahl 1.4571 27 mm Ø
- min. contact distance with several floats : 50 mm
XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
QFS-55
Teflon float switch in rod design
The float switch combination is built with float switches of the QFS-50 and QFS-60 series. This makes it possible to control a level in a simple way.
Technical Data
- Material : PTFE (Teflon)
- connection cable : Silikon, Teflon
- Material rod : VA-Rohr, PTFE beschichtet
- Operating temperature : max. +150 °C
- media density : ρ ≥ 0,75 g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- Ex-protection optional : Elektrische Daten siehe EG-Prüfbescheinigung IBExU10ATEX 1089
Reed contact
- Switching current : 1 mA ... 1 A
- Switching voltage : 24 ... 250 V AC/DC
- Switching capacity : Max. 1A, 60 VA / 60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Namur circuit (1kΩ/12kQ)
- Switching current / switching voltage : nur zum Anschluss an KR-163... oder andere „Namur”-Relais
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
T20x.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
- Box : Aluminium
- Box : Polyethylen
- Box : Kabel
- Box : Stecker
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : atmosphärisch; PP max. 90°C
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff
- LCD display : optional
- Signal output : 0…10 V | 4…20 mA
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
Operating conditions
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm
Product features
- Measuring principle : optisch, NDIR (nicht-dispersive Infrarot-Absorptionsmessung)
- Operating voltage : 24 V DC / 100 mA
- Heating time : ca. 5 min
- Response time : ca. 30 s
- Repeatability : +/- 1%
- Housing : Aluminium (rot) IP54
- Weight : ca. 500g
- Shaft range : 4,27 - 4,35 µm (4270-4350 nm)
- Gas ingress : per Diffusion
ambient conditions
- Operating temperature range : -10...+50 °C
- Storage temperature range : -40...+100 °C
- RelativeHumidity : 15..95 %
- Air pressure : 900...1100 hPa
ZMF-200e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-20X series includes sensors & transmitters for measuring gas concentrations of various gases such as CO2, methane, propane and SF-6.
This makes the sensors suitable for many applications. The ZMF-20X gas sensors are designed to be extremely rugged & suitable for use
in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- Certification : SIL2, ATEX (optional)
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0…2.000ppm : 0…0,2 % vol
- 0…5.000ppm : 0…0,5 % vol
- 0…10.000ppm : 0…1 % vol
- 0…20.000ppm : 0…2 % vol
- 0…50.000ppm : 0…5 % vol
- 0…200.000ppm : 0…20 % vol
- 0…1.000.000ppm : 0…100 % vol
Measuring Accuracy
- below 25% of the range : ±1 % FS
- below 50% of the range : 2 % FS
- above 50% of the range : ±5 % FS
LGW-13
CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
- Product type : CO2-Sensor zur Bewertung und Überwachung der Luftgüte
- Measuring principle : Basierend auf optischem Messprinzip (NDIR)
- Measuring range : Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
- Display : Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
- Switching output : Einstellbarer potentialfreier Schaltausgang
- Signal output : 4...20 mA und 0...10 V Signalausgang (nur bei der Variante L)
- Alarm : Akustischer Alarmmelder (je nach eingestellten CO2-Grenzwerten)
- further function : Integrierte Funktionsüberwachung
- Housing : Kompaktes IP 20 Wandgehäuse (Polycarbonat, weiß)
- Extension : Mögliche Erweiterung um Temperaturmessung
- Assembly : Erhältlich als Tischgerät mit Netzteil oder zur Wand- & Aufputzmontage ohne Netzteil
Technical specifications
- Standard measuring range: : 0…3.000ppm
- Optional measuring ranges: : 0…1% vol, 0…3% vol (weitere auf Anfrage)
- Accuracy : +-3% vom Messbereich (30 ppm bei 3.000 ppm)
- Relay output: : Potentialfrei
- Response time : ca. 20 s
- Operating voltage : 24 V DC, 150 mA
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!