Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
TPS-410 TPS-420
Compact, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Protection class Housing
:
IP66
Protection class plug
:
IP67
Weight
:
96g
Properties TPS-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (dew point)
:
-50…+80 °C
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
Pressure range
:
0...2.000 bar gestuft
supply
:
24 V DC
Output
:
Relais 60 V AC/1A
overload
:
1,5 x Messbereich
Med. connection
:
G 1/4 Zoll
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
T204-0
Magnetic immersion probe made of stainless steel (1.4571) as a cable tail variant
For use with highly aggressive liquid media to detect level limit values in containers. Suitable for use in hazardous areas, zone 0 (category 1).
Properties
connection
:
Polyesterdose | Aluminiumdose
Protection class EN60529
:
IP 65 Anschlussdose
Connector plug
:
3- und 6-fach
connection thread
:
G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
connection cable
:
LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
Sliding tube length
:
max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
Operating pressure
:
max. 20 bar
Viscosity
:
< 100 cp
Protection class EN60529
:
IP 68 Führungsrohr
Switching voltage
:
max. 250 V
Switching hysteresis
:
ca. 2...5 mm
Holding range
:
ca. 12 mm
Contact function
:
monostabil | bistabil
Operating temperature
ltdata.
:
max. +60...+150 °C
ltdata.
:
min. –20... –10 °C
ltdata.
:
höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
Changeover contact
:
60 W/VA
normally open
:
100 W/VA
Normally closed contact
:
60 W/VA
Switching current
Changeover contact
:
max. 1 A
NO/NC contact
:
max. 2 A
Contacts
Changeover contact
:
8
normally open
:
10
Normally closed contact
:
7
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
TK-320
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-321
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-322
:
19” Karteneinschub 7 TE, 3 HE
Properties
Protection class EN60529
:
IP 52
Operating temperature
:
– 20 °C...+60 °C
nominal voltage
:
24 V DC...230 V AC
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | Bürde max. 500 Ω
Relay
:
2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
Number of LEDs
:
33 (rot/grün); 32 (TK-322)
Resolution
:
ca. 3,5 %
Error
:
± 1 LED
connection
:
Schraubklemmen
connection TK-322
:
Steckerleiste
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | max. load 500 Ω
Relay(2xSwitch)
:
max. 230 V | min. 5 V
Relay(2xSwitch)
:
max. 3 A | min. 1 mA
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
Dimensions
:
180 x 48 x 36,5 mm ( L x B x H )
Weight
:
ca. 1,5 kg
Protection class
:
IP68
Cable length (standard)
:
15 m
Bending radius
:
> 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
Temperature range
:
0°C ... 50°C
Mounting shoe material
:
V2A 1,5mm
Certificates
EX / ATEX
:
IBExU 04 ATEX 1256
Measuring principle
Flow velocity: Ultrasonic Doppler
:
Filling level: Differential pressure
:
Flow velocity
Measuring range
:
0,01 - 4 m / s
Measuring accuracy
:
+/- 5 % vom Momentanwert im Kanal
Temperature drift
:
0,1% / °C ( Meßspanne )
Temperature drift
:
0,05% / °C ( Nullpunkt )
Output signal
:
4 - 20 mA
Filling level
Measuring ranges
:
0 –1 m ; 0 – 2 m ; 0 – 4 m
Measuring accuracy
:
< 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
Temperature drift
:
0,005% / °C v.E. Meßspanne
Temperature drift
:
0,005% / °C v.E. Nullpunkt
Material
:
Al2O3 (96%) aktive Fläche
Output signal
:
4 – 20 mA
Zero point
:
norm 4 mA ( +/- 3 % )
TK-302
Level transducer made of brass and stainless steel
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
03 (04)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
10 mm | 15 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Our application engineers advise you