Cart
product added to request
T-200.F Ex configure
BK-390 configure
XR-6x0 | XR-6x1 configure
TK-32X configure
TK-304 configure
TK-309-0 configure
HD-100 | HD-102 | HD-104 configure
ES-Serie configure
XR Relais configure
QFS-55 configure
ZMF-202e-IR configure
TRM-100 configure
T203 configure
T-200.L 230V configure
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Ex-Polyester
- Box : Ex-Aluminium
Properties
- Protection class EN60529 : IP 65
- connection thread : G2"
- Union nut : G 2¾"
- Guide tube length : max. 6 m
- Operating temperature : -20…+60 °C
- Operating pressure : max. 6 bar je nach Ausführung
- media density : ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- Ex-protection : siehe Baumusterprüfbescheinigung
- CE marking : siehe Konformitätserklärung
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- ltdata.Polyesterdose :
- ltdata.Aluminiumdose :
- ltdata.Polyethylenanschlusskopf :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- ltdata.BetriebstemperaturPP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
- Quiescent current : umschaltbar
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
- TK-320 : Schaltschrankeinbaugehäuse 24 x 96 mm
- TK-321 : Schaltschrankeinbaugehäuse 24 x 96 mm
- TK-322 : 19” Karteneinschub 7 TE, 3 HE
Properties
- Protection class EN60529 : IP 52
- Operating temperature : – 20 °C...+60 °C
- nominal voltage : 24 V DC...230 V AC
- Input : 0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
- Output : 4...20 mA | Bürde max. 500 Ω
- Relay : 2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
- Number of LEDs : 33 (rot/grün); 32 (TK-322)
- Resolution : ca. 3,5 %
- Error : ± 1 LED
- connection : Schraubklemmen
- connection TK-322 : Steckerleiste
- Input : 0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
- Output : 4...20 mA | max. load 500 Ω
- Relay(2xSwitch) : max. 230 V | min. 5 V
- Relay(2xSwitch) : max. 3 A | min. 1 mA
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
TK-304
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class Socket : IP 65
- Float type : 03, 04, 09
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar (Kugel) max. 15 bar (Zylinder)
- Resolution : 7,5 mm | 10 mm
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
- Type 09 : 0,76 g/cm³
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
- Housing : Aluminium
- Protection class : IP30
- Dimensions : 197 x 153 x 37,5mm (B x H x T)
- Temperature range : 0 – 50°C
- Supply voltage : 24V DC +/-20%
- Power consumption : 120mA – 220mA
- Reverse polarity protection : ✓
- Display : 4x20
Outputs
- analog 0(4)–20mA : 3x
- digital : 4x
- fixed for alarm : 1x
- free configurable : 3x
display of measured value
- Flow velocity :
- Filling level :
- flow :
- flow rate :
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class Socket : IP65
- Float type : Typ 07
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : Typ 07: 0,54 g/cm³
- Resolution : 7,5 mm | 10mm |15 mm | 20 mm
- Accessories : R/I-Wandler TK-101
T204.F
Immersible Magnetic Probes Ex area zone 0 (Cat 1)
Properties
- connection : Polyester Dose | Aluminium Dose
- Protection class : IP 65 Dose
- number of floats : max. 4x
- Operating temperature : max. 135 °C
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : max. 3x Wechsler | 5x Schließer | 3x Öffner
- Switching current : 1 A, 2 A (nur mit Schirmung)
- Switching voltage : 230 V AC
Float
- Stainless steel ball 52mm Ø : max. 20 bar | 0,75 g/cm³
- Stainless steel ball 61 mm Ø : max. 20 bar | 0,65 g/cm³
- Stainless steel cylinder 44 mm Ø : max. 15 bar | 0,76 g/cm³
- min. contact gap type 03 : 75 mm
- min. contact gap type 04 : 85 mm
- min. contact gap type 09 : 75 mm
Switching contacts and switching capacity
- Changeover contact : max. 3x | 60W/VA
- normally open : max. 5x | 100 W / VA
- Normally closed contact : max. 3x | 60 W/VA
HD-100 | HD-102 | HD-104
Hydrostatic immersion probes (0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP68
- Operating temperature : -10...70 °C (PVC: -10...60 °C)
- Storage temperature : -25...70 °C (PVC: -10...60 °C)
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : abhängig vom Messbereich
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik Al2o3 96%, Keramik Al2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- Cable : PVC, PUR, FEP (Ø8 mm; 2 x 0,25 mm2 mit Luftschlauch und PTFE-Filter
KST-20 Vento-RN
Climate control with aH-Controlled technology and Rn-Protected seal
The KST-20 Vento/RN is a climate control unit with aH-Controlled technology and Rn-Protected seal for ventilation and dehumidification of all types of private, commercial and industrial rooms. With the three operating modes for ventilation, dehumidification and radon measurement, the KST-20 Vento climate control unit can be used flexibly in almost all living, working and industrial areas.
Properties
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertigem ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100 % rF
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- measuring range (radon) : 0...1200 Bq/m³
- Adjustable limits : 80...1000 Bq/m³
ES-Serie
electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Weight : ca. 170g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
XR Relais
Electrode relays and contact protection relays
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
QFS-55
Teflon float switch in rod design
The float switch combination is built with float switches of the QFS-50 and QFS-60 series. This makes it possible to control a level in a simple way.
Technical Data
- Material : PTFE (Teflon)
- connection cable : Silikon, Teflon
- Material rod : VA-Rohr, PTFE beschichtet
- Operating temperature : max. +150 °C
- media density : ρ ≥ 0,75 g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- Ex-protection optional : Elektrische Daten siehe EG-Prüfbescheinigung IBExU10ATEX 1089
Reed contact
- Switching current : 1 mA ... 1 A
- Switching voltage : 24 ... 250 V AC/DC
- Switching capacity : Max. 1A, 60 VA / 60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
Namur circuit (1kΩ/12kQ)
- Switching current / switching voltage : nur zum Anschluss an KR-163... oder andere „Namur”-Relais
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. +20°...–20°
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
ZMF-202e-IR
Robust propane gas sensor for industrial applications with extended operating temperature range and ATEX / SIL-2
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0...17.000ppm : 0…1,7 vol% (100 % LEL)
- 0...21.000ppm : 0…2,1 vol%
Options
- Other cable lengths on request :
- ATEX certification (optional) :
TRM-100
Turbidimeter (0...1.000 FNU or 500...4.000 FAU)
The turbidimeter TRM-100 is a compact device for measuring turbidity in liquids. The "turbidity" is measured using the scattered light method (angle 90 degrees) for the turbidity range of < 1,000 FNU (Formazine Nephelometric Units) and the transmitted light method (angle 0 degrees) for the turbidity ranges > 1,000 FAU (Formazine Attenuation Units).
Properties
- Operating pressure : max. 10 bar @ 20 °C | max. 2,5 bar @ 60 °C
- Measuring range : 500...4.000 FNU / FAU
- Measuring accuracy : +/-5 %
- Mounting position : horizontal
- Process connection : DN 20 | DN 40
- Flange connection : >= DN 20
- number of senders : 2
- number of receivers : 1
Material
- Seal : EPDM | optional FPM (Viton)
- Process connection : PVC | PPH
- Measuring tube : Borsilikatglas mit Nano Beschichtung
Input
- Power supply : 18...30 V DC
- Power consumption : < 2 W
Output
- Output contact : 4...20 mA
- Switching delay (adjustable) : 1...10 s
- Protection class : IP 65
- Switching voltage : max. 250 V AC | max. 115 V DC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA, 60 Watt
- Potential-free changeover contact : 1 @ 1...10 s
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
- Dimensions : 180 x 48 x 36,5 mm ( L x B x H )
- Weight : ca. 1,5 kg
- Protection class : IP68
- Cable length (standard) : 15 m
- Bending radius : > 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
- Temperature range : 0°C ... 50°C
- Mounting shoe material : V2A 1,5mm
Certificates
- EX / ATEX : IBExU 04 ATEX 1256
Measuring principle
- Flow velocity: Ultrasonic Doppler :
- Filling level: Differential pressure :
Flow velocity
- Measuring range : 0,01 - 4 m / s
- Measuring accuracy : +/- 5 % vom Momentanwert im Kanal
- Temperature drift : 0,1% / °C ( Meßspanne )
- Temperature drift : 0,05% / °C ( Nullpunkt )
- Output signal : 4 - 20 mA
Filling level
- Measuring ranges : 0 –1 m ; 0 – 2 m ; 0 – 4 m
- Measuring accuracy : < 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
- Temperature drift : 0,005% / °C v.E. Meßspanne
- Temperature drift : 0,005% / °C v.E. Nullpunkt
- Material : Al2O3 (96%) aktive Fläche
- Output signal : 4 – 20 mA
- Zero point : norm 4 mA ( +/- 3 % )
T203
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
tdata.
- connection : Polyesterdose | Aluminiumdose
- Protection class : IP 65 Dose
- Guide tube : Edelstahl 1.4571, Ø 15 mm
- Guide Tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A ( nur mit Schirmung)
Float types
- float type 05 : Dichte: 0,81 g/cm³ | 110 mm Abstand
- float type 06 : Dichte: 0,67 g/cm³ | 135 mm Abstand
Number of contacts
- Changeover contact : 5x
- normally open : 6x
- Normally closed contact : 4x
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
T-200.L 230V
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!