EFV2 230V

Conductive electrodes with 24...230 V direct connection

Features

WHG Überfüllsicherung

product family

level measurement

product class

overfill protection and leackage detector

suitable for

fluids

measurement principle

conductive


Special characteristics

  • High chemical resistance

  • Adjustable response height

  • Line monitoring for cable short circuit / cable breakage

Description

The overfill protection EFV2 (24...230 V AC/DC) is approved by the "DIBt" as overfill protection for liquids hazardous to water.

Technical Data

Properties
connection
Polyesterdose (PO)
Protection class
IP 65
connection thread
G2"
Union nut
G2¾", S 100x8
Material Screw connection
PE, PVC, PPH, PVDF
Material Sensor rods
Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Kohlestifte
Operating pressure
atmosphärisch
Resistance value of line monitoring
100 kΩ
Sensitivity range
einstellbar 2..100 kΩ
Operating temperature
PE
atmosphärisch
PVC
atmosphärisch
PPH
90 °C
PVDF
100 °C
Power supply
nominal voltage
24...230 V AC/DC
Power consumption
≤ 2 W
Output
Output contact
2 potentialfreie Wechselkontakte
Switching voltage
max. 250 V AC / 30 V DC
Switching current
max. 5 A AC / 5 A DC
Switching capacity
max. 750 VA / 90 W
displays
Betriebs- LED grün Funktions-LED rot
Switching delay
ca. 0,5 s Anzug/Abfall
CE marking
siehe Konformitätserklärung

EFV2 230V configuration

Your Configuration

Basename
E
Sicherheitsfunktion
Verstellbar
Elektrodenanzahl
Verschraubungsmaterial
Stabmaterial
Anschluss
Anschlussgewinde
Elektronikteil
Standaufnehmerlänge

Further product information

Fitting and tube of the EFV2 are made of PE, PPH, PVC or PVDF. The electrode rods are made of stainless steel 1.4571, Hastelloy B, Hastelloy C, titanium, tantalum or glass-carbon pins. This makes the overfill protection suitable for use with highly aggressive media.

The EFV2 overfill protection (24...230 V AC/DC) is adjustable, the response height can be adjusted on site (see dimensional drawing).

The ET-480a electronic unit installed in the junction box supplies a measuring voltage which causes an operating current to flow through the signal line via the resistor installed in the conductive electrode. If the conductive medium rises to the level of the electrode tips of the level sensor, a circuit is closed. This leads to a switching of the potential-free output contacts on the electronic part. 

In order to cope with the different conductivities of the liquids, the sensitivity can be adjusted via the built-in potentiometer. If there is a line break, the output contacts are switched over (as with alarm by reaching the response level or voltage failure). If a line short-circuit occurs, this corresponds to an "alarm message" (as in the case of reaching the response level). The electronic part operates according to the closed-circuit current principle, i.e. in the event of a power failure, the output contacts switch as they do when the response height is reached.

  • High chemical resistance
  • Adjustable response height
  • Line monitoring for cable short circuit / cable breakage
  • Connection voltage 24...230 V AC/DC

System structure

The overfill protection can be connected to our "Optical Acoustic Alarm Devices" of the type series OAA-300.

 

Documents and Downloads

Accessoires

Benefit from our services

repair & maintenance

repair & maintenance

We produce durable products of high quality. However, if one of our products requires maintenance, we will gladly inspect the device in our Service Centre.

product development

product development

Our standard products have not yet completely convinced you? We offer customer-specific adaptation of our standard products to your wishes. Get in touch with us!

application-specific solution

application-specific solution

Are you looking for a suitable product solution for your measurement task? We recommend a product solution from our product range according to your specifications.

application-specific solution

Support & Start-up

Straightforward & fast support when things get stuck! Our support team will be glad to help you with any questions you may have about commissioning.

Our application engineers advise you personally, comprehensively and professionally!

Simply contact us by phone or e-mail!

Call us right away!

+49-6251-8462-0

contact form

Logo of Fluid.iO Sensor + Control

Fluid.iO
Sensor + Control
GmbH & Co. KG

An der Hartbrücke 6
64625 Bensheim