Sensors for temperature & humidity measurement in aluminium or polycarbonate housing
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
Housing shapes
:
Stabform | Alu- oder Polycarbonatgehäuse
measurands
:
Temperatur | relative Feuchte
Measuring range
:
-40...+80 °C | 0...100% rH
Signal output
:
0...10 V oder 4…20 mA
Power supply
:
12...30 V DC | 24 V DC
properties KG-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
properties KG-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Alu-Gehäuse mit Edelstahlstab oder Polycarbonat
Dimensions (LxBxH in mm)
:
30 x 45,4 x 97,3
Protection type/class
:
Gehäuse IP66, Stecker IP 67
Weight
:
96g
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
ZT-F
Reliable OEM pressure sensor with many customisation options (0...0,6 to 0…1.000 bar)
Can be used with all media and applications compatible with stainless steel
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
PPS-390
PPH float with magnet insert
for actuating monostable and bistable contacts
Variants
32
:
AußenØ 26 x 180 mm, für RohraußenØ 32 u. 34 mm Gewicht ca. 38 g
37
:
AußenØ 29,5 x 170 mm, für RohraußenØ 40 mm (PN 16) Gewicht ca. 62 g
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
EE-2XF
Conductive electrodes as overfill protection for Ex-Zone 0 (Cat. 1)
Conductive electrodes EE-2XF for monitoring conductive liquids within the Ex area Zone 0 (Cat. 1) for water-polluting and flammable liquids.
Properties
connection
:
Edelstahl (1.4571)
Protection class
:
IP 65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
connection thread
:
G1", G1¼", G1½”
Coating length
:
voll=ganzer Stab (10 mm am Stabende sind blank) teil =ca. 250 mm von oben
Rod diameter
:
4 oder 6 mm
rod length
:
max. 6 m
Operating pressure media side
:
max. 40 bar
Maximum permissible electrical connection values
:
Stromkreis in Zündschutzart Eigensicherheit Ex ia IIC/IIB
Connection values
:
Ui 15V | Li 10 mA | Pi 100 mW
Internal inductances / capacitances
:
vernachlässigbar klein
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Operating temperature
Category 1 Class T6...T1
:
60 °C
Category 2 Class T6
:
Medien & Umgebung 80 °C
Category 2 Class T5
:
Medien & Umgebung 95°C
Category 2 Class T4
:
Medien 130°C, Umgebung 100°C
Category 2 Class T3...T1
:
Medien 150°C, Umgebung 100 °C