32
:
AußenØ 26 x 180 mm, für RohraußenØ 32 u. 34 mm Gewicht ca. 38 g
37
:
AußenØ 29,5 x 170 mm, für RohraußenØ 40 mm (PN 16) Gewicht ca. 62 g
40
:
AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
50
:
AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
TK-302
Level transducer made of brass and stainless steel
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
03 (04)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
10 mm | 15 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
TK-301 PTFE
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
16
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 120 °C
Operating pressure
:
max. 3 bar
media density
:
0,79 g/cm³
Resolution (depending on type)
:
7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
Connection aluminium box
:
H30 x B50 x T45 mm
Connection polyester box
:
H56 x B80 x T75 mm
connection cable
:
1000 mm PUR blau
Protection class Socket
:
IP65
Material Sliding tube
:
VA 1.4571
Material of the angle fastening
:
VA 1.4408
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm
Mounting
:
2 Schlauchschellen
Accessories
:
R/I-Wandler TK-101
T20x.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
EE-2X
electrode, multiple for Ex-Zone 0 (Cat. 1)
The conductive electrodes of the EE-21/EE-22 series enable the monitoring of conductive liquids within the Ex area Zone 0 (Cat. 1).
Variants
cable connection on side
:
EE-21
cable connection on top
:
EE-22
Properties
connection
:
Edelstahl (1.4571)
Protection class EN60529
:
IP65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6