The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
connection
:
G 1” (andere Gewinde auf Anfrage)
max.length guide tube
:
siehe Diagramm
Operating temperature
:
atmosphär. Bedingungen
Operating pressure
:
atmosphär. Bedingungen
media density
:
siehe Eintauchtiefe
Number of contacts
:
beliebig
Contact load
:
max. 10 VA, max. 230 V AC
Length
:
max. 1750 mm
Material
Sight tube
:
PVC transparent
connection
:
PVC-Verschraubung mit PTFE-Stangenführung
Guide rod
:
Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
float
:
PE / PP
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff mit LCD-Anzeige (oponal)
Overpressure
:
1,2* (1,5*) x Nenndruck
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Signal output selection
:
0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
Pressure range
:
5…1.000 bar
Operating conditions
Operating voltage
:
14...28 VDC ± 10 %
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
Connections
Electrical connection
:
Schraubklemme im Gehäuse
Process connection
:
G1/4" (andere auf Anfrage)
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
Our application engineers advise you
personally, comprehensively and professionally!