T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
07
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Accessories
:
R/I-Wandler TK-101
TK-304
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class Socket
:
IP 65
Float type
:
03, 04, 09
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar (Kugel) max. 15 bar (Zylinder)
Resolution
:
7,5 mm | 10 mm
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Type 09
:
0,76 g/cm³
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
Our application engineers advise you