ciA Standards
:
Ds301 Version 4.2 & DS401 Version 3.0
ISO standards
:
ISO11898 (+ Transceiver TJA1050)
PDO
:
siehe Dokumente
TK-301
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
05 (06)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm| 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 05
:
0,81 g/cm³
Type 06
:
0,67 g/cm³
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
Our application engineers advise you