Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
Power supply
:
230 V AC
measuring range (CO2)
:
0..10.000 ppm
Measuring accuracy CO2
:
± 50ppm +3 % vom Messwert
Operating conditions
:
0…50°C / 0…85 %rH
Storage conditions
:
-30…70°C / 0…85 %rH
Protection class
:
IP 31
EMV/ESD
:
EN 50082-1, EN 50082-2
Signal output
:
I²C
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties TPS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…100% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-50...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
KS-410 KS-420
Sensors for temperature & humidity measurement in aluminium or polycarbonate housing
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Specifications
Housing shapes
:
Stabform | Alu- oder Polycarbonatgehäuse
measurands
:
Temperatur | relative Feuchte
Measuring range
:
-40...+80 °C | 0...100% rH
Signal output
:
0...10 V oder 4…20 mA
Power supply
:
12...30 V DC | 24 V DC
properties KG-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
properties KG-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Alu-Gehäuse mit Edelstahlstab oder Polycarbonat
Dimensions (LxBxH in mm)
:
30 x 45,4 x 97,3
Protection type/class
:
Gehäuse IP66, Stecker IP 67
Weight
:
96g
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
HD-100 | HD-102 | HD-104
Hydrostatic immersion probes (0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
Protection class EN60529
:
IP68
Operating temperature
:
-10...70 °C (PVC: -10...60 °C)
Storage temperature
:
-25...70 °C (PVC: -10...60 °C)
Power supply
:
15...30 V DC
power
:
max. 25 mA
Output
:
2-Leiter-Technik
Measuring range
:
0,8...10 mWs (Standard)
Overpressure
:
abhängig vom Messbereich
Deviation from characteristic curve
:
Nichtlinearität,
Insulation resistance
:
> 100 kΩ
Short-circuit resistance
:
permanent
Reverse polarity protection
:
keine Schädigung o. Funktion bei vertauschten Anschlüssen