The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
Tank connection
:
Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
Material
:
siehe Maßbild
Material Tube
:
PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
Operating temperature
:
–20...+60 °C
Operating pressure
:
atmosphärisch
Material Float
PPH
:
Ø 70 mm 460 g
PVC
:
Ø 70 mm 455 g
PPH
:
Ø 40 mm 370g
PE
:
Ø 70 mm ca. 450 g
Material Rope
PPH
:
(rot, Ø 2 mm) ~ 2 g/m
Polyester
:
(bunt, Ø 2 mm) ~ 4 g/m
PTFE
:
(weiss, Ø 3 mm) ~ 10 g/m
QFS-5x | QFS-6x
Teflon float switch for all kinds of liquids up to 150°C
The float of the QFS-50 and QFS-60 float switches is made of Teflon. Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Switching current / switching voltage
:
nur zum Anschluss an KR-163... oder andere „Namur”-Relais
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. +20°...–20°
HD-100 | HD-102 | HD-104
Hydrostatic immersion probes (0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
Protection class EN60529
:
IP68
Operating temperature
:
-10...70 °C (PVC: -10...60 °C)
Storage temperature
:
-25...70 °C (PVC: -10...60 °C)
Power supply
:
15...30 V DC
power
:
max. 25 mA
Output
:
2-Leiter-Technik
Measuring range
:
0,8...10 mWs (Standard)
Overpressure
:
abhängig vom Messbereich
Deviation from characteristic curve
:
Nichtlinearität,
Insulation resistance
:
> 100 kΩ
Short-circuit resistance
:
permanent
Reverse polarity protection
:
keine Schädigung o. Funktion bei vertauschten Anschlüssen