CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
ViscoScope® VA-300
Maintenance-free inline process viscometer for real-time viscosity measurement
The ViscoScope® sensors are made of high-quality, first-class stainless steel and impress with their intelligent, robust design.
Properties
- Protection class : IP65
- Material : 1.4571 / 1.4404 (316Ti / 316L)
- Process temperature : -40°C … +450°C
- Process pressure : Vakuum ... 450 bar
- Process connections : DIN Flansch | ANSI Flansch | NPT | Varivent® | Tri-Clamp
- Cable length sensor - transmitter : max. 1.000m
- max. flow velocity : 10 m / sec
- Ex approval : (optional) II 1/2G Ex ia IIC T6...T3 Ga/Gb
- Material (optional) : Hastelloy C22, Duplex 2205, Teflon
Sensor types
- big cylinder : VA-300L
- small cylinder : VA-300M
- Sphere : VA-300H
- small sphere : VA-300X
Measuring range
- VA-300L : 0,1 - 2.500 mPa·s x g/cm³
- VA-300M : 1 - 25.000 mPa·s x g/cm³
- VA-300H : 0,01...250 Pa·s x g/cm³
- VA-300X : 0,1...2.500 Pa·s x g/cm³
Probe dimensions
- VA-300L : Ø 32 x 190 mm
- VA-300M : Ø 32 x 165 mm
- VA-300H : Ø 32 x 130 mm
- VA-300X : Ø 19 x 115 mm
EFV2 20…230V
Conductive electrodes with 24...230 V direct connection
The overfill protection EFV2 (24...230 V AC/DC) is approved by the "DIBt" as overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾" | S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Kohlestifte
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Adjustable sensitivity range : 2..100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Power supply
- nominal voltage : 24...230 V AC/DC
- Power consumption : ≤ 2 W
Output
- potential-free changeover contacts : 2
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs- LED grün Funktions-LED rot
- Switching delay : ca. 0,5 s
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
T-200.L 230V
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
T204-0.F
Immersible Magnetic Probe for Ex Zone 0 (Cat. 1)
The T20... magnetic immersion probes are used to detect fill level limits in containers for liquid media, where an explosive atmosphere of Zone 0 (Cat. 1) exists in the gas space above the liquid and an Ex-Zone 1 (Cat. 2) exists outside the container in the area of the junction box.
Properties
- connection : Kabel PUR blau
- Protection class : IP 68 Dose
- number of floats : max. 4x
- Operating temperature : max. 135 °C
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : max. 3x Wechsler | 5x Schließer | 3x Öffner
- Switching current : 1 A, 2 A (nur mit Schirmung)
- Switching voltage : 230 V AC
Float
- Stainless steel ball 61 mm Ø : max. 20 bar | 0,65 g/cm³
- min. contact gap type 04 : 85 mm
Switching contacts and switching capacity
- Changeover contact : max. 3x | 60W/VA
- normally open : max. 5x | 100 W / VA
- Normally closed contact : max. 3x | 60 W/VA
T-20X
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
Our application engineers advise you personally, comprehensively and professionally!