The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
Pressure range
:
0...500mbar gestuft
supply
:
12 - 24 V DC
Output
:
Relais 230 V/1A
overload
:
2 x Messbereich
Med. connection
:
Schlauch
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
Housing
:
Kunststoff
Power supply 24V
:
24V DC | 230V
Measuring element and parameter
Measuring principle
:
optisch, NDIR
measuring grid
:
2 sec.
Accuracy
:
± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
connection
:
integrierter Anschlusskopf
Protection class
:
IP 65
connection thread
:
G 1¼"
Material Screw connection
:
PPH
Material electrode rods
:
Edelstahl (1.4571), Hastelloy C, Titan, Tantal
material coating
:
PTFE
Coating length
:
voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
Rod diameter
:
4 mm, 6 mm
rod length
:
max. 6 m
Operating temperature
:
85 °C
Operating pressure
:
atmosphärisch
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
Operating temperature
:
–20...+85 °C
Storage temperature
:
–30...+85 °C
nominal voltage
:
24 V DC ± 15%
Power consumption
:
max. 2 W (Klemme A1, A2)
Switching voltage
:
max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
Switching current
:
max. 3 A AC, 3 A DC min. 1 mA
Switching capacity
:
max. 750 VA, 150 W
Sensitivity
:
3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
TK-30X
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
connection thread
:
G 3/8”, G 1/2”, G 1”, G 1 1/2”, G 2”, G 3”
connection cable
:
LiYY max. 80 °C | Silikon max. 130 °C
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. +60...+130 °C | min. –20...–10 °C je nach Ausführung
Operating pressure
:
max. 20 bar je nach Ausführung
media density
:
siehe Schwimmerdaten
Viscosity
:
< 100 cp
Switching hysteresis
:
ca. halbe Auflösung
Resolution
:
7,5 mm, 10 mm, 15 mm, 20 mm oder 1 %, 2 %, 5 % je nach Ausführung
Total resistance
:
ca. 5 kΩ
Measuring voltage
:
max. 24 V
Measuring current
:
max. 5 mA
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
T200 Ex
Magnetic immersion probes with TÜV 02 ATEX 1795X approval for Ex zone 0
Magnetic immersion probes for detecting fill level limit values in containers for liquid media, where an explosive atmosphere of zone 0 (category 1) is present in the gas space above the liquid and zone 1 (category 2) outside the container in the area of the junction box
Properties
connection
:
Polyesterdose | Aluminiumdose
Protection class EN60529
:
IP 65 Anschlussdose
Connector plug
:
3- und 6-fach
connection thread
:
G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
connection cable
:
LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
Sliding tube length
:
max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
Operating pressure
:
max. 20 bar
Viscosity
:
< 100 cp
Protection class EN60529
:
IP 68 Führungsrohr
Switching voltage
:
max. 250 V
Switching hysteresis
:
ca. 2...5 mm
Holding range
:
ca. 12 mm
Contact function
:
monostabil | bistabil
Operating temperature
ltdata.
:
max. +60...+150 °C
ltdata.
:
min. –20... –10 °C
ltdata.
:
höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
Changeover contact
:
60 W/VA
normally open
:
100 W/VA
Normally closed contact
:
60 W/VA
Switching current
Changeover contact
:
max. 1 A
NO/NC contact
:
max. 2 A
Contacts
Changeover contact
:
8
normally open
:
10
Normally closed contact
:
7
Our application engineers advise you