Cart
product added to request
ZT-S configure
ES-22 configure
GSB-390 configure
EF2...5 configure
ZT-F configure
TK-309 configure
T-20x.F 230V configure
XR-4x0 | XR-4x1 configure
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- ltdata.MessbereichNenndruck : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- ltdata.Medientemperatur(optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- ltdata.Standard : Binder M12 x 1
ES-22
electronic safety pressure limiter with 2 safety functions
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
GSB-390
Glass float with magnet insert
for actuating monostable and bistable contacts
Variants
- 150 : AußenØ 26,5 x 150 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 50 g
- 190 : AußenØ 26,5 x 190 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 61 g
- 205 : AußenØ 26,5 x 205 mm (3 Magnete auch für bistabile Kontakte) Gewicht ca. 69 g
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
ZT-F
Reliable OEM pressure sensor with many customisation options (0...0,6 to 0…1.000 bar)
Can be used with all media and applications compatible with stainless steel
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
T209-0.F
Magnetic immersion probe overfill protection for Ex zone 0 (Cat. 1)
The magnetic immersion probes T20... are used to detect fill level limit values in containers for liquid media, where an explosive atmosphere of zone 0 (cat. 1) is present in the gas space above the liquid and Ex zone 1 (cat. 2) is present outside the container, in the area of the junction box.
Properties
- connection : Polyesterdose, Aluminiumdose
- Protection class : IP 65 Dose
- Float type : Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135°C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : 6x Wechsler, 9x Schließer, 6x Öffner
- Switching current : 1A, 2A ( nur mit Schirmung)
- Switching capacity : Wechsler: 60 W/VA, Schließer: 100 W/VA Öffner: 60 W/VA
- min. contact distance with several floats : 125 mm
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 07
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- media density : Typ 07: 0,54 g/cm³
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
- Accessories : R/I-Wandler TK-101
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80°C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!