The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
10 (14)
connection cable
:
1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating pressure
:
max. 6 bar
Resolution
:
10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
CE marking
:
siehe Konformitätserklärung
Operating temperature
PV
:
max. 60°C
PE
:
max 80 °C
PP
:
max. 90°C
MaterialDensity
Type 10
:
0,72 g/cm³
Type 14
:
0,72 g/cm³
Type 18
:
0,82 g/cm³
OAA-300
Alarm Indicator (Measuring Transducer) with general approval for construction
Our alarm indicators type OAA-300 are stand-alone signaling devices with optic and acoustic alarm indication.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
– 20…+60 °C
Storage temperature
:
– 30…+80 °C
Sensitivity
:
bei konduktiver Messung: 3, 10, 30, 100kΩ
Dimensions
:
170 x 190 x 85 mm
Weight
:
ca. 0,8 kg
Control circuits
Open circuit voltage
:
max. 10 V DC
Short-circuit current
:
max. 10 mA
Switching delay
:
ca. 0,5 s
Power supply
nominal voltage
:
230 V AC (optional 24, 115, 240 V AC 24 V DC
Nominal frequency
:
48...62 Hz
Power consumption
:
max. 3 W/VA
Output
Switching voltage
:
max. 250 V
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA | max. 50 W
Volume
:
75 dB
Our application engineers advise you