Cart
EF 3…5 24 V configure
T203.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Properties
- Protection class : IP 65 Dose
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A
- Switching voltage : 230 V AC
Float
- quantity : max. 6
- Type 05 : Oval Edelstahl 76 mm Ø | Dichte 0,81 g/cm³
- Type 06 : Oval Edelstahl 90 mm Ø | Dichte 0,67 g/cm³
- Minimum contact distance : Typ 05: 110 mm | Typ 06: 135 mm
Switching contacts and switching capacity
- Changeover contact : max. 5x | 60 W/VA
- normally open : max. 6x | 100 W/VA
- Normally closed contact : max. 4x | 60 W/VA
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- connection : integrierter Anschlusskopf
- Protection class : IP 65
- connection thread : G 1¼"
- Material Screw connection : PPH
- Material electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- material coating : PTFE
- Coating length : voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
- Rod diameter : 4 mm, 6 mm
- rod length : max. 6 m
- Operating temperature : 85 °C
- Operating pressure : atmosphärisch
- Spacer : ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24 V DC ± 15%
- Power consumption : max. 2 W (Klemme A1, A2)
- Switching voltage : max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
- Switching current : max. 3 A AC, 3 A DC min. 1 mA
- Switching capacity : max. 750 VA, 150 W
- Sensitivity : 3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Polyester junction box :
- Aluminum housing :
- Polyethylene connection head :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- PP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
Our application engineers advise you personally, comprehensively and professionally!