The vibrating limit switch is a level limit switch for all kinds of fluids and is used in tanks, containers and pipelines.
Properties
Protection class EN60529
:
IP 65/IP 67
Operating pressure
:
≤ 40 bar
media density
:
ρ ≥ 0,7 g/cm³
Viscosity
:
max. 10000 mm²s
Rated current
:
< 15 mA
Protection class
:
III
Output
:
PNP
power
:
kurzschlussfest, überlastsicher
Display
:
LED (grün, rot)
Switching delay (cover)
:
ca. 0,5 s
Switching delay (release)
:
ca. 1 s
NSP-1-E
connection thread
:
G 1”
Operating temperature
:
–40...+150 °C
Storage temperature
:
–40...+85 °C
nominal voltage
:
10...55 V DC (verpolsicher)
Current output
:
≤ 350 mA
NSP-2-E
connection thread
:
G ½”
Operating temperature
:
–40...+100 °C
Storage temperature
:
–20...+70 °C
nominal voltage
:
10...35 V DC (verpolsicher)
Current output
:
≤ 250 mA
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
Housing
:
Aluminium
Protection class
:
IP30
Dimensions
:
197 x 153 x 37,5mm (B x H x T)
Temperature range
:
0 – 50°C
Supply voltage
:
24V DC +/-20%
Power consumption
:
120mA – 220mA
Reverse polarity protection
:
✓
Display
:
4x20
Outputs
analog 0(4)–20mA
:
3x
digital
:
4x
fixed for alarm
:
1x
free configurable
:
3x
display of measured value
Flow velocity
:
Filling level
:
flow
:
flow rate
:
ZMF-203e-IR
Robust sulphur hexafluoride sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-203e-IR is an SF6 sensor for measuring sulphur hexafluoride concentration in harsh environments.
Properties
Operating conditions
:
-40 °C…+60 °C
Storage conditions
:
-40 °C…+85 °C
RelativeHumidity
:
0…95 % nicht kondensierend
Measurement method
:
NDIR (dual beam technology)
Certification
:
SIL2, ATEX
Signal output
:
4..20mA
Power supply
:
12…24 V DC
Housing
:
Edelstahl
Standard cable length
:
1,5 m
pressure conditions
:
800...1200 mbar
screw thread
:
M46x15
Measuring ranges
in ppm
:
in vol%
0...1.000ppm
:
0...0,1 vol%
0...2.000ppm
:
0...0,2 vol%
Options
Other cable lengths on request
:
ATEX certification (optional)
:
TK-302
Level transducer made of brass and stainless steel
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
03 (04)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
10 mm | 15 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Our application engineers advise you