Cart
BK-380 configure
HD-110 | HD-112 | HD-114 configure
TK-301 PTFE configure
TK-300 configure
LU-1X0 configure
KG-2XX configure
TK-312 configure
PPS-390 configure
BK-380
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
TK-301 PTFE
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 16
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 120 °C
- Operating pressure : max. 3 bar
- media density : 0,79 g/cm³
- Resolution (depending on type) : 7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
- Housing : Robustes Aluminiumgehäuse
- Operating voltage : 18...36V DC (max. 400 mA @18V)
- Dimensions : 150 x 119 x 82 mm (L x B x H)
Operating conditions
- Operating temperature: : 0...+70 °C (optional 0...+90 °C)
- Maximum operating pressure: : 10 bar (optional 30 bar)
- Storage temperature: : -40...+90 °C
Connection
- ModBus TCP/IP : Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
- Digital I/O ports : 1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
- User Interface : grafisch über Weboberfläche im eingebundenen Netzwerk
T209-0
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : PO-Dose oder AA-Dose
- Protection class : IP 65 Dose
- Float type : max. 6x Kugel Edelstahl 105 mm Ø
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- media density : 0,54 g/cm³
- Number of contacts : max. 7x Wechsler / max. 10x Schließer / 7x Öffner
- Switching current : 1A, 2A
- Switching capacity : Wechsler 60W/VA | Schließer 100 W/VA | Öffner 60 W/VA
- min. contact distance with several floats : 125 mm
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
- connection : Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 10 (14)
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
- CE marking : siehe Konformitätserklärung
Operating temperature
- PV : max. 60°C
- PE : max 80 °C
- PP : max. 90°C
MaterialDensity
- Type 10 : 0,72 g/cm³
- Type 14 : 0,72 g/cm³
- Type 18 : 0,82 g/cm³
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA, 2W
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0-4...10 kW
Output
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Current output : 0/4... 20 mA bezogen auf die Masse des Eingangs
- Voltage output : 0/2... 10 V
- Mounting : Tragschiene nach EN 50022
- Weight : 175 g
PPS-390
PPH float with magnet insert
for actuating monostable and bistable contacts
Variants
- 32 : AußenØ 26 x 180 mm, für RohraußenØ 32 u. 34 mm Gewicht ca. 38 g
- 37 : AußenØ 29,5 x 170 mm, für RohraußenØ 40 mm (PN 16) Gewicht ca. 62 g
- 40 : AußenØ 40 x 165 mm, für RohraußenØ 50 mm Gewicht ca. 145 g
- 50 : AußenØ 50 x 125 mm, für RohraußenØ 63 mm Gewicht ca. 156 g
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!