Cart
product added to request
KST-20 Calima configure
EF2 24...230 V configure
TK-101 EX configure
BK-390 configure
Lub-VDT USB-Kit
Software and USB kit for configuration & evaluation
Properties
- details : folgen
KST-20 Calima
Climate control for automatic & controlled dehumidification, ventilation and cooling of rooms
The KST-20 Calima climate control system with aH-Controlled technology for ventilation and dehumidification for all types of private, commercial and industrial rooms. With the operating modes for living room ventilation and room dehumidification, the KST-20 Calima can be used flexibly in almost all living, working and industrial areas.
Specifications
- measuring range (Humidity) : 0…100% rF,
- Measuring accuracy (humidity) : ±2%
- measuring range (Temperature) : -40…+80°C
- Measuring accuracy (temperature) : ±0,2°C
- Signal output : I2C
- Connections for actuators : Zwei Steuer- und Schaltausgänge für Zuluft- und Abluftelemente
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 140x140x46 mm
Connection options
- Dehumidification : Einstufige Lüftungsventilatoren
- Room dehumidification / living space ventilation : Zweistufige Lüftungsventilatoren
- Living space ventilation / Dehumidification : Drehzahlgesteuerte Ventilatoren 0…10 V DC
Operating conditions
- Temperature : 0...50 °C
- RelativeHumidity : 85 % nicht kondensierend
- EMV/ESD : EN50082-1/2
EF2 24...230 V
Conductive electrodes with 24...230 V direct connection
The EF2 overfill protection (24...230 V AC/DC) is approved by "DIBt" as an overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G1"
- Union nut : auf Wunsch
Material
- Screw connection : PE, PVC, PPH, PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Sensitivity range : einstellbar 2…100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PTFE : 100 °C
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : < 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC /30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED Grün, Funktions-LED Rot
- Switching delay : ca. 0,5 s Anzug / Abfall
- CE marking : siehe Konformitätserklärung
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
- measuring range (Humidity) : 0…100 % rF,
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- Signal output : I2C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000…1.500 ppm
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
- measuring range (Humidity) : 0...100 % rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80 °C
- Measuring accuracy (temperature) : ± 0,2 °C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000...1.500 ppm
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!