Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
EK-CAN
PC program for CANopen sensors
Evaluation and configuration software for Fluid.iO CANopen sensors
Properties
Operating system
:
tba.
available disc space
:
tba.
scrren resolution
:
tba.
softwatre architecture
:
tba.
software type
:
tba.
installation type
:
tba.
BK-380
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
–25...+70 °C
Wire cross-section max.
:
1,5mm²
Switching point distance between two contacts
:
min. 40 mm
Switching hysteresis
:
ca. 10-15 mm
Material
Housing
:
Polycarbonat
Mounting clip
:
V2A, Kabelbinder (PP)
Rivet
:
V2A
Screw connection
:
M 20 x 1.5, Polyamid
Weight
BK-390-50
:
137 g
BK-390-63 / BK-380
:
140 g
Switching contact
Switching voltage
:
5...250 V AC/DC
Switching current
:
1mA...6 A AC/DC
Switching capacity(min.)
:
300 VA, 60 W
Switching capacity(max.)
:
5 mW
Smart Pressostat App
App for control of ES-2X devices over Bluetooth
Android app for Bluetooth communication between smartphone or tablet and electronic safety switching devices from Fluid.iO
Properties
platform
:
Android
Android Version
:
12
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
details
:
folgen
T208
Immersible Magnetic Probe made of PVC, PE, PPH
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
connection
:
Polyesterdose | Aluminiumdose
Protection class EN60529
:
IP 65 Anschlussdose
Connector plug
:
3- und 6-fach
connection thread
:
G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
connection cable
:
LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
Sliding tube length
:
max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
Operating pressure
:
max. 20 bar
Viscosity
:
< 100 cp
Protection class EN60529
:
IP 68 Führungsrohr
Switching voltage
:
max. 250 V
Switching hysteresis
:
ca. 2...5 mm
Holding range
:
ca. 12 mm
Contact function
:
monostabil | bistabil
Operating temperature
ltdata.
:
max. +60...+150 °C
ltdata.
:
min. –20... –10 °C
ltdata.
:
höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
Changeover contact
:
60 W/VA
normally open
:
100 W/VA
Normally closed contact
:
60 W/VA
Switching current
Changeover contact
:
max. 1 A
NO/NC contact
:
max. 2 A
Contacts
Changeover contact
:
8
normally open
:
10
Normally closed contact
:
7
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
Operating voltage
:
12...32 V DC (max. 0,2 W)
Dimensions
:
Ø 22 x 59 (D x H), SW22
Housing
:
Edelstahl
Measuring range nominal pressure
:
-1…500 bar
Overpressure
:
2 x Nenndruck
Bursting pressure
:
4 x Nenndruck
Protection class
:
IP65
Output signal
:
ZILA-DIO
Operating conditions
Pressure type
:
Relativdruck
Temperature of the fluid
:
-40 …+125 °C
fluid temperature (optional)
:
-20 …+125 °C
Ambient temperature
:
-40 …+105 °C
electrical connection
Standard
:
Binder M12 x 1
ZS-2
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
Pressure type
:
Differenzdruck
Housing
:
Aluminium
medium
:
Luft und nicht aggressive Gase
Measurement parameters
response time
:
< 2,5 s
Hysteresis
:
0,1 %
Overload capacity
:
4* fach bis 500 mbar, darüber 2* fach
Signal output selection
:
0...10 V | 4...20 mA, 2-Leiter
Process connection
:
Schlauchanschluss 4 mm oder 6 mm
Cable gland
:
PG 7
Pressure measuring range
0...2,5mbar
:
0...5mbar
:
0...10mbar
:
0...25mbar
:
0...50mbar
:
0...100mbar
:
0...250mbar
:
0...500mbar
:
0...1.000mbar
:
TK-302
Level transducer made of brass and stainless steel
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
03 (04)
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
Resolution
:
10 mm | 15 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
connection thread
:
G 1/2” Standard | G 3/4” | G1”
Cable
:
TPK (Standard) | SIL (Silikon) | FEP (Teflon)
rod length
:
max. 6.000 mm
Operating pressure
:
max. 40 bar
Material
electrode body
:
Edelstahl 1.4571
Process connection
:
Edelstahl 1.4571
Coating
:
PTFE
electrode rod
:
Edelstahl 1.4571
on request
:
Hastelloy C | Tantal
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class Socket
:
IP65
Float type
:
Typ 07
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10mm |15 mm | 20 mm
Accessories
:
R/I-Wandler TK-101
ZMF-202e-IR
Robust propane gas sensor for industrial applications with extended operating temperature range and ATEX / SIL-2
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
Operating conditions
:
-40 °C…+60 °C
Storage conditions
:
-40 °C…+85 °C
RelativeHumidity
:
0…95 % nicht kondensierend
Measurement method
:
NDIR (dual beam technology)
Certification
:
SIL2, ATEX
Signal output
:
4..20mA
Power supply
:
12…24 V DC
Housing
:
Edelstahl
Standard cable length
:
1,5 m
pressure conditions
:
800...1200 mbar
screw thread
:
M46x1,5
Measuring ranges
in ppm
:
in vol%
0...17.000ppm
:
0…1,7 vol% (100 % LEL)
0...21.000ppm
:
0…2,1 vol%
Options
Other cable lengths on request
:
ATEX certification (optional)
:
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
connection
:
G 1” (andere Gewinde auf Anfrage)
max.length guide tube
:
siehe Diagramm
Operating temperature
:
atmosphär. Bedingungen
Operating pressure
:
atmosphär. Bedingungen
media density
:
siehe Eintauchtiefe
Number of contacts
:
beliebig
Contact load
:
max. 10 VA, max. 230 V AC
Length
:
max. 1750 mm
Material
Sight tube
:
PVC transparent
connection
:
PVC-Verschraubung mit PTFE-Stangenführung
Guide rod
:
Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
float
:
PE / PP
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff mit LCD-Anzeige (oponal)
Overpressure
:
1,2* (1,5*) x Nenndruck
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Signal output selection
:
0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
Pressure range
:
5…1.000 bar
Operating conditions
Operating voltage
:
14...28 VDC ± 10 %
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
Connections
Electrical connection
:
Schraubklemme im Gehäuse
Process connection
:
G1/4" (andere auf Anfrage)
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
-10...70 °C
Storage temperature
:
-25...70 °C
Power supply
:
15...30 V DC
power
:
max. 25 mA
Output
:
2-Leiter-Technik | 4...20 mA
Measuring range
:
0,8...10 mWs (Standard)
Overpressure
:
ca. 20 %
Deviation from characteristic curve
:
Nichtlinearität,
Insulation resistance
:
> 100 kΩ
Short-circuit resistance
:
permanent
Reverse polarity protection
:
keine Schädigung o. Funktion bei vertauschten Anschlüssen