The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
–25...+70 °C
Wire cross-section max.
:
1,5mm²
Switching point distance between two contacts
:
min. 40 mm
Switching hysteresis
:
ca. 10-15 mm
Material
Housing
:
Polycarbonat
Mounting clip
:
V2A, Kabelbinder (PP)
Rivet
:
V2A
Screw connection
:
M 20 x 1.5, Polyamid
Weight
BK-390-50
:
137 g
BK-390-63 / BK-380
:
140 g
Switching contact
Switching voltage
:
5...250 V AC/DC
Switching current
:
1mA...6 A AC/DC
Switching capacity(min.)
:
300 VA, 60 W
Switching capacity(max.)
:
5 mW
TK-304
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class Socket
:
IP 65
Float type
:
03, 04, 09
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar (Kugel) max. 15 bar (Zylinder)
Resolution
:
7,5 mm | 10 mm
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Type 09
:
0,76 g/cm³
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
Housing
:
Aluminium, eloxiert
Measuring element humidity
:
kapazitiv, betauungsfest
Measuring element temperature
:
Halbleiter
measuring resolution
:
12 Bit
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Option
:
Bereistellung des EDS-Files
tdata.
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Minimum air velocity across the sensor required for measurement
:
1,5 m/s
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Ex-Polyester
Box
:
Ex-Aluminium
Properties
Protection class EN60529
:
IP 65
connection thread
:
G2"
Union nut
:
G 2¾"
Guide tube length
:
max. 6 m
Operating temperature
:
-20…+60 °C
Operating pressure
:
max. 6 bar je nach Ausführung
media density
:
ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
Ex-protection
:
siehe Baumusterprüfbescheinigung
CE marking
:
siehe Konformitätserklärung
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
Pressure range
:
0...500mbar gestuft
supply
:
12 - 24 V DC
Output
:
Relais 230 V/1A
overload
:
2 x Messbereich
Med. connection
:
Schlauch
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
07
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Accessories
:
R/I-Wandler TK-101
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
EF2 24...230 V
Conductive electrodes with 24...230 V direct connection
The EF2 overfill protection (24...230 V AC/DC) is approved by "DIBt" as an overfill protection for liquids hazardous to water.